5.3.4 Digital 280-1 with measured value output
ConF / Out.3: O.tYP = 1 Out.3 0...20mA continuous
= 2 Out.3 4...20mA continuous
= 3 Out.3 0...10V continuous
= 4 Out.3 2...10V continuous
Out.0 = -1999...9999 scaling Out.3
for 0/4mA or 0/2V
Out.1 = -1999...9999 scaling Out.3
for 20mA or 10V
O.Src=3 signal source for Out.3 is
the process value
Configuration level
Digital 280-1 Configuration examples 33
phys.
unit
mA / V
phys. unit
Out.1
Out.0
0/4mA
0/2V
20mA
10V
U
Logic
OUT3
7
8
9