PMA Prozeß- und Maschinen-Automation GmbH Digital 280-1 digital indicator Digital 280-1 Digital 280-1 Operating manual English 9499-040-67311 Valid from: 8495
û BlueControl More efficiency in engineering, more overview in operating: The projecting environment for the BluePort® controllers n o ! s N e t O a I pd de T N U e. E and nlin D T ATrsion ma-o A-C e .p PM V ni ww r on i M w o Description of symbols in the text: on the device: g General information a Follow the operating instructions a General warning l Attention: ESD-sensitive devices © PMA Prozeß- und Maschinen-Automation GmbH • Printed in Germany All rights reserved.
Inhaltsverzeichnis 1 2 2.1 2.2 3 3.1 3.2 3.3 3.3.1 3.3.2 3.3.3 3.3.4 3.3.5 3.3.6 3.4 4 4.1 4.2 4.3 4.3.1 4.3.2 4.3.3 4.3.4 4.3.5 4.4 4.5 5 5.1 5.2 5.3 5.3.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . 6 Connecting diagram. . . . . . . . . . . . . . . . . . . . . . . . . 6 Terminal connection . . . . . . . . . . . . . . . . . . . . . . . . 6 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.2 5.3.3 5.3.4 6 6.1 6.2 6.3 4 2-point controller (inverse) . . . . . . . . . . . . . . . . . . . . . . . 31 Continuous controller (inverse) . . . . . . . . . . . . . . . . . . . . . 32 Digital 280-1 with measured value output . . . . . . . . . . . . . . . 33 Parameter setting level . Parameter survey . . . . Parameter . . . . . . . . Input scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting 1 Mounting ) 4" 92 +0,8 (3.62" +0.03 ) " .65 10 (4 8 11 48 (1.89") (1.89") min.48 (1.77" +0.02) ") .4 .0 0 4. .0 .1 1. (0 45 +0,6 . (0 Digital 280-1 OUT1 OUT2 max. 60°C min. 0°C max. 95% rel. % OUT3 ADA FUNC ERR F min max 96 (3.78") ) Loc 10V i mA/Pt security switch or Ü Ü * * Loc 10V mA/Pt Safety switch: For access to the safety switches, the indicator must be withdrawn from the housing.
Electrical connections 2 Electrical connections 2.1 Connecting diagram Option 1 6 di2 (2) 3 6 di3 7 UT 4 5 6 7 2 RXD-B RGND 8 4 4 5 6 g h i 7 10 8 11 9 13 RXD-A 14 TXD-A RS485 15 g 17 RS422 * 7 OUT3 5 8 U 9 12 16 DATA A OUT1 OUT2 Logic 9 GND TXD-B DATA B 1 3 8 Modbus RTU 90...
Electrical connections Connection of input di1 3 Digital input, configurable as switch or push-button Connection of outputs OUT1/2 4 Relay outputs 250V/2A normally open with common contact connection Connection of output OUT3 5 logic (0..20mA / 0..12V) voltage (0/2...10V) current (0/4...
Electrical connections 6 OUT 3 als Logikausgang mit Solid-State-Relais (Reihen- und Parallel-Schaltung) serial installation parallel installation 3 4 Imax=22mA 5 SSR _ 4V 6 + Logic Imax=22mA SSR _ 7 4V 12V 8 7 9 12V 8 + SSR _ + 9 SSR _ SSR _ 4V 10 + + 9 RS485 interface (with RS232-RS485 interface converter) * 12 12 RGND DATA B RT DATA A 12 12 10 10 13 13 RGND 11 14 14 12 15 15 14 14 DATA B 13 (16) 16 14 17 17 15 13 13 DATA A 15 15 (16) 16 17 17 12 12 10
Electrical connections Connecting exampleDigital 280-1: L1 L2 fuse fuse Digital 280-1 1 1 22 2 contactor 33 33 4 4 5 5 6 Logic fuse TB 40-1 1 temperature limiter 7 8 6 SSR _ 7 8 + 9 9 10 10 10 11 11 11 12 12 12 13 13 13 14 14 14 15 15 15 + heating + resetswitch N1 N2 1 TB 40-1 temperature limiter standard-version (3 relay) TB40-100-0000D-000 r further versions on demand a CAUTION: Using a temperature limiter is recommendable in systems where overtemperature implies a
Operation 3 Operation 3.1 Front view Digital 280-1 2 3 4 5 6 OUT1 OUT2 1 OUT3 ADA FUNC ERR F 0 min max 7 1 2 3 4 5 6 7 8 9 0 g 8 9 measured value display statuses of switching outputs OuT.1...
Operation 3.3 Operating level 3.3.1 Min/max function The minimum and maximum values are stored. Digital 280-1 Digital 280-1 OUT1 OUT1 OUT2 OUT2 OUT3 OUT3 ADA ADA FUNC FUNC ERR ERR Ì Ì max min Digital 280-1 Digital 280-1 OUT1 OUT1 OUT2 OUT2 OUT3 OUT3 ADA ADA FUNC FUNC ERR ERR As long as the Ì key is pressed, the minimum value is displayed. As long as the È key is pressed, the maximum value is displayed.
Operation 3.3.2 Tare function When switching on the tare function, the instantaneous measured value is set to zero. In this case, measurement is continued with this offset. By switching off the tare function, the actual measured value is displayed again. measured value effective value è è ADA FUNC ERR è ADA FUNC ERR t ADA FUNC ERR Tare can be activated during configuration (Func r Fnc.1 = 1).
Operation 3.3.4 O2 measurement For measurement, lambda probes (l probes) are used. The electromotive force (in Volt) supplied by the l probes is dependent of the instantaneous oxygen content and of the temperature. Therefore, Digital 280-1 can display accurate measurement results only, provided that the probe temperature is known to the indicator. Enter the temperature in °C in parameter tEmP. When using heated l probes, the probe temperature can be entered directly.
Operation 3.3.5 Extended operating level The content of the extended operating level is determined by means of BlueControl (engineering tool). Parameters which are important or which are used frequently can be copied into the extended operating level. Actuating key Ù switches to the first value of the extended operating level (may be Digital 280-1 preceded by error list or set-point). The selected parameters can be changed by pressing keys Ì and È.
Operation 3.3.6 Alarm handling Max. three alarms can be configured and assigned to the individual outputs. Generally, outputs OuT.1... OuT.3 can be used each for alarm signalling. If more than one signal is linked to one output the signals are OR linked. Each of the 3 limit values Lim.1 … Lim.3 has 2 trigger points H.x (Max) and L.x (Min), which can be switched off individually (parameter = “OFF”). Switching difference HYS.x of each limit value is adjustable. Operaing principle absolut alarm L.1 = OFF InL.
Operation g g The variable to be monitored can be selected seperately for each alarm via configuration The following variables can be monitored: w process value w control deviation xw (process value - set-point) w control deviation xw + suppression after start-up or set-point change As there is automatically a control deviation after starting up and after set-point changes, however, the alarm is suppressed, until the signal was within the limits once.
Controller 4 Controller In addition to the simple indicator function, Digital 280-1 can be used also as a signaller or an on/off controller, as a two point or a continuous controller. Prerequisite: Digital 280-1 is fitted with option “with outputs” and is configured for the controller function. Configuration: Function 2 provides selection between indicator and controller: Func r Fnc.2 Controller 4.
Controller 4.3 Self-tuning After starting by the operator, the controller makes a self-tuning attempt. The controller uses the process characteristics for quick line-out to the set-point without overshoot. g g Self-tuning start can be locked via BlueControl (engineering tool) ( P.Loc). ti and td are taken into account only, if they were ¹ OFF previously. 4.3.1 Self-tuning start ( Ù + È ) Digital 280-1 OUT1 The operator can start self-tuning at any time.
Controller Error-Status Selfoptimization Error status 0 3 4 5 6 7 8 Description Behaviour No error Faulty control action Re-configure controller (inverse i direct) No response of process variable The control loop is perhaps not closed: check sensor, connections and process Low reversal point Increase ( ADA.H) max. output limiting Y.Hi or decrease ( ADA.C) min. output limiting Y.
Controller Start: heating power switched off The controller waits 1,5 minutes (1). Heating power Y is switched on (2). At the reversal point, the self-tuning attempt is finished and control to the set-point is using the new parameters. X W t 100% Y 0% start r 1 Start: at set-point Heating power Y is switched off (1). If the change of process value X was constant during one minute and the control deviation is > 10% of SP.Hi SP.LO (2), the power is switched on (3).
Controller The control parameters can be determined from the values calculated for delay time Tu , maximum rate of increase vmax, control range Xh and characteristic K according to the formulas given below. Increase Xp, if line-out to the set-point oscillates.
Controller 4.5 Operating structure After supply voltage switch-on, the controller starts with the operating levels. Digital 280-1 3s OUT1 Digital 280-1 Ù OUT2 OUT3 ADA FUNC ERR OUT1 Ù OUT2 OUT3 ADA FUNC PASS ERR Digital 280-1 Ì OUT1 Ù OUT2 OUT3 ADA FUNC PASS ERR Digital 280-1 Ì OUT1 Ù OUT2 OUT3 ADA FUNC PASS ERR Digital 280-1 Ì OUT1 Ù OUT2 OUT3 ADA FUNC ERR g PArA - level: At PArA - level, the right decimal point of the upper display line is lit continuously.
Configuration level 5 Configuration level 5.1 Configuration survey O.tYP O.Act Y.1 Lim.1 Lim.2 Lim.3 FAi.1 OuT.0 Out.1 O.Src L_r Err.r tArA HOLd rES.L rES.H di.Fn End Othr Display, operation, interface LOGI digital Inputs OUt.3 Output 3 OUt.2 Output 2 È Fnc.1 StYP Fnc.1 Ì Fnc.2 S.Lin Src.1 See output 1 OUt.1 Output 1 C.Fnc Corr Fnc.2 C.Act Src.2 rnG.L Fnc.3 rnG.H Src.3 O.Act Y.1 Lim.1 Lim.2 Lim.3 FAi.
Configuration level 5.2 Configuration Dependent of instrument version and configuration, spare parameters are not displayed. Func name description function 1 0 no function 1 tare - function 2 sample & hold 3 O2 - measuring Fnc.2 function 2 0 indicator 1 controller C.Fnc controller behavior (algorithm) 0 on/off controller e.g. signaller with one output 1 PID-controller (2-point and continuous) C.Act operating principle of the controller 0 inverse, e.g. heating 1 direct, e.g. cooling rnG.L -19999...
Configuration level name value range description default 41 special (-2,5...115 mV scaling necessary r page36) 42 special (-25...1150 mV scaling necessary r page 36) 43 special (-25...90 mV scaling necessary r page 36) 44 special (-500...500 mV scaling necessary r page 36) 45 special (-5...5 V scaling necessary r page 36) 50 potentiometer 0...160 Ohm 51 potentiometer 0...450 Ohm 52 potentiometer 0...1600 Ohm 0 S.Lin linearization only adjustable with S.tYP: 18, 23, 24, 30, 40 ...
Configuration level Out.1 und Out.2 name O.Act value range 0 1 Y.1 0 1 Lim.1 Lim.2 Lim.3 FAi.1 0 1 0 1 fOut 0 1 description circuit direction of output OUT1 direct / open circuit principle inverse / closed circuit priciple controller output Y1 not active active message limit value 1/2/3 not active active message INP error not active active forcing OUT1 (2) (only visible with BlueControl!) no forcing forcing via interface default 0 0 Out.1/2/3 0 0 Out.3 name O.tYP O.Act Y.1 Lim.1 Lim.2 Lim.
Configuration level name value range description default 1 O.Src signalsource for analog output OUT3 (only visible with O.TYP=1..
Configuration level name rES.H value range description default 0 0 2 3 4 5 di.
Configuration level name value range description default 0 C.dEl modem delay [ms] 0 switch-over 50/60 Hz (only visible with BlueControl!) FrEq 0 netfrequency 50 Hz 1 netfrequency 60 Hz 0 blocked selfoptimization (only visible with BlueControl!) IAdA 0 free 1 blocked 0 extended operation level blocked (only visible with BlueControl!) IExo 0 free 1 blocked suppression error memory ILat 0 free 1 blocked OFF...99999 OFF password -19999 ...
Configuration level 5.3 Configuration examples 5.3.1 On-Off controller / Signaller (inverse) InL.1 SP.LO SP SP.Hi InH.1 InP.1Ê 100% SH Out.1Â 0% ConF / Cntr: SP.Fn C.Fnc C.Act ConF / Out.1: PArA / Cntr: PArA / SEtP: O.Act Y.1 SH SP.LO SP.Hi = 0 = 0 = 0 set-point controller signaller with one output inverse action (e.g. heating applications) = 0 action Out.1 direct = 1 control output Y1 active = 0...9999 switching difference (symmetrical to the trigger point) = -1999...
Configuration level 5.3.2 2-point controller (inverse) InL.1 SP.LO InP.1Ê SP SP.Hi InH.1 PB1 100% Out.1Â 0% ConF / Cntr: SP.Fn=0 C.Fnc = 1 C.Act = 0 ConF / Out.1: PArA / Cntr: PArA / SEtP: g O.Act Y.1 Pb1 ti1 td1 t1 SP.LO SP.Hi set-point controller 2-point controller (PID) inverse action (e.g. heating applications) = 0 action Out.1 direct = 1 control output Y1 active = 0,1...9999 proportional band 1 (heating) in units of phys. quantity (e.g. °C) = 1...9999 integral time 1 (heating) in sec.
Configuration level 5.3.3 Continuous controller (inverse) SP.LO InL.1 InP.1Ê SP SP.Hi InH.1 PB1 20 mA Out.3Â 0/4 mA ConF / Cntr: SP.Fn=0 C.Fnc = 1 C.Act = 0 ConF / Out.3: PArA / Cntr: PArA / SEtP: g g 32 O.tYP Out.0 Out.1 Pb1 = = = = 1/2 -1999...9999 -1999...9999 0,1...9999 ti1 td1 t1 SP.LO SP.Hi = = = = = 1...9999 1...9999 0,4...9999 -1999...9999 -1999...9999 set-point controller continuous controller (PID) inverse action (e.g. heating applications) Out.
Configuration level 5.3.4 Digital 280-1 with measured value output phys. unit Out.1 mA / V phys. unit Out.0 0/4mA 0/2V 20mA 10V Logic 7 OUT3 8 U 9 ConF / Out.3: O.tYP Out.0 Out.1 = -1999...9999 O.Src=3 Digital 280-1 1 2 3 4 -1999...9999 = = = = = Out.3 0...20mA continuous Out.3 4...20mA continuous Out.3 0...10V continuous Out.3 2...10V continuous scaling Out.3 for 0/4mA or 0/2V scaling Out.3 for 20mA or 10V signal source for Out.
Parameter setting level 6 Parameter setting level 6.1 Parameter survey Depending on unit version and configuration spare parameters are not shown. Ì tEmP Pb1 ti1 td1 t1 SH Y2 Y.Lo Y.Hi Y0 SP.LO SP.Hi InL OuL InH OuH tF b.F E.tc End Lim Limits È InP Input Func Functions PArA Parameter-Level L.1 H.1 HYS.1 dEL.1 L2 H.2 HYS.2 dEL.2 L.3H.3 HYS.3 HYS.3 dEL.
Parameter setting level 6.2 Parameter Func name tEmP Pb1 ti1 td1 t1 SH Y2 value range description default 1...99999 1 probetemperature for O2 measuring 650 1...99999 1 proportional band in phys. unit (z.B. °C) 100 1...99999 180 reset time 1 [s] (ti1=0 = off = switched off) 1...99999 180 derivative time1 (heating) [s] (td1=0 = off = switched off) 0,4...99999 10 min. cycle duration1 (heating) [s]. The smallest pulse duration is 1/4 x t1 0...9999 2 neutral zone, e.g. switching difference signalunit [phys.
Parameter setting level 6.3 Input scaling When using current or voltage signals as input variables for InP.1 or InP.2, scaling of input and display values at parameter setting level is required. Specification of the input value for lower and higher scaling point is in the relevant electrical unit (mA / V). phys. unit OuH.x phys. unit mA / V OuL.x InL.x InH.x mA/V 6.3.1 Input Inp g a 36 Parameters InL.1 , OuL.1, InH.1 and OuH.1 are only visible if ConF / InP.1 / Corr = 3 is chosen.
Calibration level 7 Calibration level g Measured value correction ( CAL) is only visible if ConF / InP.1 / Corr = 1 or 2 is chosen. The measured value can be matched in the calibration menu ( CAL). Two methods are available: 7.1 Offset correction ( ConF/ InP.1 / Corr =1 ): display standard-setting Offset-correction possible on-line at the process OuLnew OuLold InL 2-point correction Display Standardeinstellung 2-Punkt-Korrektur ( ConF/ InP.
Calibration level Offset correction ( ConF/ InP.1 / Corr =1 ): Digital 280-1 OUT1 OUT2 OUT3 ADA FUNC ERR r r Ù r PArA 3 sec. Ì ConF r Ì CAL r Ù r InPr Ù r InL r Ù È InL Ù r OuL È Ù Ì r End r Ù InL.1: The input value of the scaling point is displayed. The operator must wait, until the process is at rest. Subsequently, the operator acknowledges the input value by pressing key Ù. OuL.1: The display value of the scaling point is displayed. Before calibration, OuL.1 is equal to InL.1.
Calibration level 2-point correction ( ConF/ InP.1 / Corr =1 ): Digital 280-1 OUT1 OUT2 OUT3 ADA FUNC r Ù r PArA 3 sec. Ì r ERR ConF r Ì CAL r Ù r InP r Ù r InL r Ù È InL Ù OuL È rÙ Ì InH rÙ È InH Ù OuH È rÙ Ì r End r Ù InL.1: The input value of the lower scaling point is displayed. The operator must adjust the lower input value by means of a process value simulator and confirm the input value by pressing key Ù. OuL.1: The display value of the lower scaling point is displayed.
BlueControl 8 BlueControl BlueControl is the projection environment for the BluePort â controller series of PMA.
Versions 9 Versions Digital 280-1 D 2 8 0 1 Connection via screw-terminal 90..250V AC 24VAC / 18..30VDC 90..250V AC, 2 relay+ mA/V/logic 24VAC / 18..
Technical data 10 Technical data INPUTS Switched voltage: Current: PROCESS VALUE INPUT INP1 CONTROL INPUTS DI2, DI3 (OPTION) Resolution: Decimal point: > 15 bits 0 to 4 digits behind the decimal point Limiting frequency: 2 Hz (analog) Dig. input filter: adjustable 0,1...
Technical data OUT3 AS UNIVERSAL OUTPUT Galvanically isolated from the inputs. Freely scalable Resolution: Timeconstant of DA-transducer T90 Limitfrequency of the whole continuous controller 11 Bit 50 ms > 2 Hz Current output 0/4...20 mA configurable. Signal range: Max. load: Load effect: Resolution: Accuracy 0...ca.21,5 mA £ 500 W 0,02 % / 100 W £ 22 mA (0,1%) £ 40 mA (0,2%) Voltage output (short-circuit proof) 0/2...10V configurable Signal range: Min. load: Load effect: Resolution: Accuracy 0...ca.
Technical data Protocol: Modbus RTU Transmission speed: 2400, 4800, 9600, 19.200 bits/sec Address range: 1...247 Number of controllers per bus: 32 Repeaters must be used to connect a higher number of controllers.
Technical data Tabelle 1 thermocouple measuring range thermocouple type L J K N S R T C D E B(1) Fe-CuNi (DIN) Fe-CuNi NiCr-Ni Nicrosil/Nisil PtRh-Pt 10% PtRh-Pt 13% Cu-CuNi W5%Re-W26%Re W3%Re-W25%Re NiCr-CuNi PtRh-Pt6% special (1) measuring range -100...900°C -148...1652°F -100...1200°C -148...2192°F -100...1350°C -148...2462°F -100...1300°C -148...2372°F 0...1760°C 32...3200°F 0...1760°C 32...3200°F -200...400°C -328...752°F 0...2315°C 32...4199°F 0...2315°C 32...4199°F -100...1000°C -148...
Safety hints 11 Safety hints a This unit was built and tested in compliance with VDE 0411-1 / EN 61010-1 and was delivered in safe condition. The unit complies with European guideline 89/336/EWG (EMC) and is provided with CE marking. The unit was tested before delivery and has passed the tests required by the test schedule. To maintain this condition and to ensure safe operation, the user must follow the hints and warnings given in this operating manual.
Safety hints a MAINTENANCE, REPAIR AND MODIFICATION The units do not need particular maintenance. Warning When opening the units, or when removing covers or components, live parts and terminals may be exposed. Before starting this work, the unit must be disconnected completely. After completing this work, re-shut the unit and re-fit all covers and components. Check if specifications on the type label must be changed and correct them, if necessary.
Index 0-9 2-point correction. . . . . . . . . . . . 37 A Alarm handling . . . . . . . . . . . . . 15 Anschlußbeispiele OUT3 als Logikausgang . . . . . 8 B BlueControl. . . . . . . . . . . . . . . 40 Bus interface Technical Data. . . . . . . . . . 43 C Calibration (CAL) . . . . . . . . . . . 37 Calibration level (CAL) . . . . . . 37 - 39 Configuration examples 2-point controller . . . . . . . . 31 Signaller . . . . . . . . . . . . . 30 Configuration level Parameter survey . . . . . . . .
A5 auf A6 gefaltet 2-fach geheftet, SW-Druck, Normalpapier 70g weiß Subject to alterations without notice Änderungen vorbehalten Sous réserve de toutes modifications © PMA Prozeß- und Maschinen-Automation GmbH P.O.B.