Owner manual
Name Value range Description
O.Src
Signal source for analog output OUT3 (only visible with O.TYP=1..4 )
0 Not active
3 Process value
7 Measured value INP1
8 Measured value INP2 µ
O.FAI
Fail behaviour
0 Upscale
1 Downscale
Inf.1 Status message Inf.1 (operating hours) (visible only with BlueControl!)
0 Not active
1 Active
Inf.2 Status message Inf.2 (number of switching cycles) (visible only with BlueControl!)
0 Not active
1 Active
fOut Forcing OUT3 (only visible with BlueControl!)
0 Not active
1 The value for this output is preset via interface
Logic LOGI
Name Value range Description
di.Fn
Function of inputs (valid for all inputs)
0 Direct
1 Invers
2 toggle key function (adjustable for 2-point-operation with interface and di1)
L_r
Local / remote switchover
(Remote: Adjustment of all values via the front panel is blocked)
0 No function (switch-over via interface is possible)
1 Always active.
2 Di1 switches.
7 Limit 1 switches
8 Limit 2 switches
9 Limit 3 switches
Err.r
Source for resetting all stored entries in the error list
0 No function (switch-over via interface is possible)
2 Di1 switches.
7 Limit 1 switches
8 Limit 2 switches
9 Limit 3 switches
I.ChG
Switching the effective process value between INP1 and INP2.
µ (input 2 must be released (CONF / Inp.2 / I.Fnc = 1))
0 No function (switch-over via interface is possible).
2 Di1 switches.
7 Limit 1 switches
8 Limit 2 switches
9 Limit 3 switches
Configuration level
UNIFLEX CI 45 Configurations 43