Owner manual

Name Value range Description
24 Special 0...450 Ohm
25 Special 0...1600 Ohm
26 Special 0...160 Ohm
30 0...20mA / 4...20 mA
40 0...10V / 2...10 V (Inp.1 only)
41 Special (-2,5...115 mV)
42 Special (-25...1150 mV)
43 Special (-25...90 mV)
44 Special (-500...500 mV)
45 Special (-5...5 V) (Inp.1 only)
46 Special (-10...10 V) (Inp.1 only)
47 Special (-200..200 mV)
50 Potentiometer 0...160 Ohm
51 Potentiometer 0...450 Ohm
52 Potentiometer 0...1600 Ohm
53 Potentiometer 0...4500 Ohm
4wir
Resistance connection type (Inp.1 only)
0 3-wire connection
1 4-wire connection
S.Lin
Linearization only adjustable with S.tYP:18, 23 ... 47
0 none
1 Special linearization. Producing a linearization table is possible via BlueControl
(Engineering-Tool). Preset is the characteristic for KTY 11-6 temperature sensors.
Corr
Measured value correction / scaling
0 No correction
1 Offset correction (at CAL -level)
2 2-point correction (at CAL -level)
3 Scaling (at PArA -level)
In.F
OFF,
-1999...9999
Substitute value in case of a fault. This value is used for calculations, if there is a
fault at the input (e.g. FAIL).
fAI1
(fAI2)
Forcing of analog input INP1, INP2 µ (only visible with BlueControl!)
0 Not active
1 The value for this analog input is preset via interface
Counter / frequency input µ
Name Value range Description
I.Fnc
Function selection µ
0 Control input
1 Up counter, positive edge
2 Up counter, negative edge
3 Down counter, positive edge
4 Down counter, negative edge
5 Frequency measurement
Frq.t
0,1…20 Frequency gate time [s] µ
Configuration level
40 Configurations UNIFLEX CI 45