6.15.4 Frequency output (optional)
The analog output signal for voltage can be selected also as a frequency output with setting:
ConF / Out.3: O.tYP = 6 Out.3 0...10V frequency output
Setting O.Src defines the signal source of the frequency output value.
Example: O.Src = 3 signal source for Out.3 is the process value
Output range scaling is done via parameter pairs Out.L/ FrQ.L and Out.H/ FrQ.H. Values Out.L and
Out.H are specified in physical units, FrQ.L and FrQ.H are specified in Hz.
Example:
20°C = 5Hz
200°C = 500 Hz
Settings: Ou.L = 20; Frq.L = 5,0
Ou.H = 200; Frq.H = 500,0
The output behaviour in case of input value error can be defined via O.FAI .
g
Please, note that the lower the span the higher the effect of input variations and resolution steps
g
Signals exceeding the permissible frequency range cause deviations from the square shape of frequency
waves.
6.15.5 Analog output forcing
By adjusting f.Out = 1 (only via BlueControl), the output can be configured for value input via interface, or by means of
an input value at extended operating level (=Forcing).
g
This setting can be used also for e.g. testing the cables and units connected in the output circuit.
g
This function can also realize a setpoint potentiometer.