Owner's manual

Resolution of PV and Setpoint on CALogix-sw can be set as 0.01, 0.1 or 1. This resolution is also the format used for the corresponding
data register with CALogix unit to be read by an operator panel or for data acquisition. It is recommended that display setting of 0.01 is NOT
used when a thermocouple or PT100 sensor is used as the displayed value will fluctuate.
Setpoint 1 upper limit Sensor Max -9999 to 9999 step 0.01
Sets a maximum permissible value for Setpoint 1
Setpoint 1 Lower limit Sensor Min -9999 to 9999 step 0.01
Seets a minimum permissible value for Setpoint 1
Span Offset 0.0 -9999 to 9999 step 0.01
Realigns readings to match another instrument e.g. calibration source or meter see note on recalibration.
Zero offset 0.0 -9999 to 9999 step 0.01
Zero sensor error. +ve zero offset increases measured PV, -ve zero offset reduces measured PV, see note on recalibration.
Linear High 50.0 0.0 to 50.0 step 0.1
Configures maximum linear input see Linear inputs
Linear Low 10.0 0.0 to 50.0 step 0.1
Configures minimum linear input, see Linear inputs
Linear high scale 1000 -9999 to 9999 step 0.01
Scale controller to display value at Linear high value
Linear low scale 0 -9999 to 9999 step 0.01
Scale controller to display value at Linear low value
Module * - Output settings Default Options
Setpoint 1 output None Output 1, Output 2, Output 3
Select physical output to be assigned as Setpoint 1.
Setpoint 2 output None Output 1, Output 2, Output 3
Select physical output to be assigned as Setpoint 2
Setpoint 3 output None Output 1, Output 2, Output 3
Select physical output to be assigned as Setpoint 3
Output 1, 2 & 3 burnout state De-energised De-energised, Energised
Configure state of outputs on sensor burnout / break
Output 1, 2 & 3 inversion False False, True
Reverse operation of outputs
Output 1 inhibit None None, Output 2, Output 3
Prevents other outputs energising at the same time as Output1
Output 1,2 & 3 cycle count - Count value (Read only)
Each module internally stores a read-only value of the number of cycles for each output, this can be used to check the estimated remaining
life of a mechanical relay, if fitted.
Module * – Setpoint 1 control Default Options
Setpoint 1 0 -9999 to 9999, step 0.01
Change setpoint 1 value
Mode Park P, PI, PID, PD, Park, On/Off
Primary control type for setpoint 1
P Proportional
PI Proportional Integral
PID Proportional Integral Derivative
PD Proportional Derivative
Park Holds controller operation – disables output
On/Off On/Off Control
Band 10 0 to 9999, step 0.01
SP1 proportional band or Hysteresis -* 100% sensor maximum, proportional control eliminates the cycling of on-off control. Output power
is varied, by proportioning action, across the proportional band
Integral Time 5 mins 0 to 9999, step 0.1
SP1 integral time/reset - Auto-corrects proportional control offset error
Derivative time 25 secs 0 to 200, step 1
SP1 derivative time/rate - Suppresses overshoot and speeds response to disturbances
DAC 2 0.5 to 8, step 0.5
SP1 derivative approach control dAC - Tunes warm-up characteristics, independent of normal operating conditions, by adjusting
when derivative action starts during start-up (smaller dAC value = nearer setpoint).
Page 21 of 44