Manual

1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
Page 86 P6700, P8700& P4700 Model Group 59305, Issue 7 March 2014
Parameter
Lower
Display
Upper
Display
Description
Default
Value
When
Visible
Decimal point
position


Decimal point position in
non-temperature ranges.
0 = XXXX
1 = XXX.X
2 = XX.XX
3 = X.XXX

=
mV, V or
mA



Process
Variable Offset

Span of controller (see CAUTION note
at end of section)

Always
Limit Action


High Limit. Limit relay is
energised when process
“safe” (PV < Limit Setpoint)

Always

Low Limit. Limit relay is
energised when process
“safe” (PV > Limit Setpoint)
Setpoint Upper
Limit

Current Setpoint value to Scale Range
Maximum
Range
Max.
Always
Setpoint Lower
Limit

Scale Range Minimum to current Setpoint
value
Range
Min
Always
Alarm 1Type


Process High Alarm

Always

Process Low Alarm

Deviation Alarm

Band Alarm

No alarm
Process High
Alarm 1 value*

Range Min. to Range Max.
Range
Max.
=

Process Low
Alarm 1 value*

Range Min. to Range Max
Range
Min.
=

Deviation
Alarm 1 Value*

span from setpoint

=

Band Alarm 1
value*

1 LSD to full span from setpoint.

=

Alarm 1
Hysteresis*

1 LSD to 100% of span (in display units)
on “safe” side of alarm point.

Always
Alarm 2 Type

As for alarm 1 type

Always
Process High
Alarm 2 value*

Range Min. to Range Max.
Range
Max.
=

Process Low
Alarm 2 value*

Range Min. to Range Max.
Range
Min.
=

Deviation
Alarm 2 Value*

span from setpoint.

=

Band Alarm 2
value*

1 LSD to full span from setpoint.

=
