Manual

1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
59305, Issue 7 March 2014 P6170, P8170 & P4170 Model Group Page 77
Upper
Display
Lower
Display
When Visible
Description
SP Value

Display strategy 1, 3,
4, 5 and 6 if Digital
Input is not  in
config mode and
RSP is not used.
Target value of Setpoint.
Adjustable except in Strategy 6
SP1 Value

or

Display strategies 1
to 6, if Digital Input is
set for dual SP
( in config
mode).
Target value of Setpoint 1.  means
SP1 is selected as the active Setpoint.
Adjustable except in Strategy 6
SP2 Value

or

Display strategies 1
to 6, if Digital Input is
set for dual SP
( in config
mode).
Target value of Setpoint 2.  means
SP2 is selected as the active Setpoint.
Adjustable except in Strategy 6
Local Setpoint
Value


or

If Remote Setpoint
Input is fitted and
Digital Input is not
 in config
mode
Target value of Local Setpoint. 
means the local setpoint is selected as the
active SP (if the digital input has been
overridden, the character is lit instead).
Adjustable except in Strategy 6
Remote
Setpoint
Value


or

If Remote Setpoint
Input is fitted and
Digital Input is not
 in config
mode
Target value of Remote Setpoint. 
means the remote setpoint is selected as
the active SP (if the digital input has been
overridden, the character is lit instead).
Read only
Valve Position
Value
xxx
Display strategy 7 if
position indication
enabled ( or
 = )
The valve position as read by the Auxiliary
Input. Position is expressed as a
percentage from  (fully closed) to
 (fully opened).


or


If Remote Setpoint
Input is fitted, Digital
Input is not  in
config mode and
 is enabled in
Setup mode
Setpoint Select. Selects between Local or
Remote Setpoints.
 = local SP,  = remote SP, 
= selection via digital input (if configured).
Note:  or  will override the digital
input (active SP indication changes to )
Adjustable except in Strategy 6
Actual SP
Value

If a Ramping
Setpoint is in use
( not Blank).
Actual value of selected Setpoint (e.g.
ramping SP value). Read only
SP Ramp
Rate Value

If  (ramping SP)
is enabled in Setup
mode.
Setpoint ramping rate, in units per hour.
Set to Blank (higher than ) to turn off
ramping. Adjustable except in Strategy 6