- DIN Controllers & Indicators - Product Manual
Page 74 P6170, P8170 & P4170 Model Group 59305, Issue 7 – March 2014
Table 17. P6170, P8170 & P4170 Set Up Mode Parameters
Parameter
Lower
Display
Upper Display
Adjustment Range
Default
Value
When
Visible
Input Filter Time
constant
OFF, 0.5 to 100.0 secs in
0.5 sec increments
.
Always
Process Variable Offset
Span of controller
Always
Primary Output
Proportional Band
0.5% to 999.9% of input
span.
.
Always
Automatic Reset
(Integral Time
Constant)
0.01 to 99.59 (1 sec to 99
mins 59 secs) and OFF
.
Always
Rate (Derivative Time
Constant)
0.00 to 99.59 (OFF to 99
mins 59 secs)
.
Always
Setpoint Upper Limit
Current Setpoint value to
Scale Range Maximum
Range
Max.
Always
Setpoint Lower limit
Scale Range Minimum to
current Setpoint value
Range Min
Always
Minimum Motor On
Time
0.0 to (Motor Travel
Time/10) secs in 0.1 sec
increments
.
Always
Set Valve Opened
Position
Aux. Input value when
valve is fully opened.
Note: See above for
setting instructions
Auxiliary
Input
Range
Maximum
or =
Set Valve Closed
Position
Aux. Input value when
valve is fully closed.
Note: See above for
setting instructions
Auxiliary
Input
Range
Minimum
or =
Valve Open Limit
Value position max. clamp
+1 to .
or =
Valve Close Limit
Value position min. clamp
to -1
or =
Process High Alarm 1
value*
Range Min. to Range
Max.
Range
Max.
=
Process Low Alarm 1
value*
Range Min. to Range
Max.
Range
Min.
=
Deviation Alarm 1
Value*
span from setpoint
=
Band Alarm 1 value*
1 LSD to full span from
setpoint.
=
Alarm 1 Hysteresis*
Up to 100% of span
Always
Process High Alarm 2
value*
Range Min. to Range
Max.
Range
Max.
=
Process Low Alarm 2
value*
Range Min. to Range
Max.
Range
Min.
=