Manual

1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
Page 66 P6170, P8170 & P4170 Model Group 59305, Issue 7 March 2014
Parameter
Lower
Display
Upper
Display
Description
Default
Value
When
Visible
Input type and
Range
(Continued)


Pt100: -199 to 800 ºC

for Europe

for USA
Always

Pt100: -328 to 1472 ºF

Pt100: -128.8 to 537.7 ºC
with decimal point

Pt100: -199.9 to 999.9 ºF
with decimal point

0 to 20mA DC

4 to 20mA DC

0 to 50mV DC
 
10 to 50mV DC

0 to 5V DC

1 to 5V DC

0 to 10V DC

2 to 10V DC
Scale Range
Upper Limit

Scale Range Lower Limit +100 to Range
Max
Linear
inputs =
1000
(°C/°F
inputs =
max
range)
Always
Scale Range
Lower Limit

Range Min. to Scale range Upper Limit -
100
Linear = 0
(°C/°F =
min range)
Always
Decimal point
position


Decimal point position in
non-temperature ranges.
0 = XXXX
1 = XXX.X
2 = XX.XX
3 = X.XXX

=
mV, V or
mA



Control Action


Reverse Acting

Always

Direct Acting
Motor Travel
Time

. to .
(0 mins 5 secs to 5 mins 0 secs)

Always
Alarm 1Type


Process High Alarm

Always

Process Low Alarm

Deviation Alarm

Band Alarm

No alarm