- DIN Controllers & Indicators - Product Manual
Page 52 P6100, P8100 & P4100 Model Group 59305, Issue 7 – March 2014
Parameter
Lower
Display
Upper Display
Adjustment Range
Default
Value
When
Visible
Output 2
Cycle Time
0.5, 1, 2, 4, 8, 16, 32, 64,
128, 256 or 512 secs.
Not applicable to linear
outputs
=
or
or
Output 3
Cycle Time
0.5, 1, 2, 4, 8, 16, 32, 64,
128, 256 or 512 secs.
Not applicable to linear
outputs
=
or
or
Process High Alarm 1
value*
Range Min. to Range
Max.
Range
Max.
=
Process Low Alarm 1
value*
Range Min. to Range
Max.
Range
Min.
=
Deviation Alarm 1
Value*
span from setpoint
=
Band Alarm 1 value*
1 LSD to full span from
setpoint.
=
Alarm 1 Hysteresis*
Up to 100% of span
Always
Process High Alarm 2
value*
Range Min. to Range
Max.
Range
Max.
=
Process Low Alarm 2
value*
Range Min. to Range
Max.
Range
Min.
=
Deviation Alarm 2
Value
span from setpoint
=
Band Alarm 2 value*
1 LSD to full span from
setpoint.
=
Alarm 2 Hysteresis*
Up to 100% of span
Always
Loop Alarm Time*
1 sec to 99 mins. 59secs.
Only applies if primary
proportional band = 0
=
Auto Pre-tune enable /
disable
disabled or
enabled
Always
Manual Control select
enable / disable
disabled or
enabled
Always
Setpoint Select shown
in Operator Mode,
enable / disable
disabled or
enabled
Slot A or B fitted
with RSP module
Setpoint ramp shown in
operator mode, enable /
disable
disabled or
enabled
Always
SP Ramp Rate Value
1 to 9999 units/hour or Off
(blank)
Blank
Always