59305, Issue 7 – March 2014 P6100, P8100 & P4100 Model Group Page 51
Table 12. P6100, P8100 & P4100 Set Up Mode Parameters
Parameter
Lower
Display
Upper Display
Adjustment Range
Default
Value
When
Visible
Input Filter Time
constant
OFF, 0.5 to 100.0 secs in
0.5 sec increments
.
Always
Process Variable Offset
Span of controller
Always
Primary Power
The current Primary
Output Power. Read Only.
N/A
Always
Secondary Power
The current Secondary
Output power. Read Only.
N/A
=
Primary Output
Proportional Band
0.0% (ON/OFF control)
and 0.5% to 999.9% of
input span.
.
Always
Secondary Output
Proportional Band
0.0% (ON/OFF control)
and 0.5% to 999.9% of
input span.
.
=
Automatic Reset
(Integral Time
Constant)
0.01 to 99.59 (1 sec to 99
mins 59 secs) and OFF
.
is not .
Rate (Derivative Time
Constant)
0.00 to 99.59 (OFF to 99
mins 59 secs)
.
is not .
Overlap/Deadband
-20% to +20% of the sum
of the Primary and
Secondary Proportional
Bands
is not .
Manual Reset (Bias)
0% to 100% (-100% to
100% if = )
is not .
Primary Output
ON/OFF Differential
0.1% to 10.0% of input
span (enter in % span)
.
= .
Secondary Output
ON/OFF Differential
0.1% to 10.0% of input
span (enter in % span)
.
= .
Primary and Secondary
Output ON/OFF
Differential
0.1% to 10.0% of input
span (enter in % span)
.
and
= .
Setpoint Upper Limit
Current Setpoint value to
Scale Range Maximum
Range
Max.
Always
Setpoint Lower limit
Scale Range Minimum to
current Setpoint value
Range Min
Always
Primary (Heat) Output
Upper Power Limit
0% to 100% of full power
is not .
Output 1
Cycle Time
0.5, 1, 2, 4, 8, 16, 32, 64,
128, 256 or 512 secs.
Not applicable to linear
outputs
=
or
or