Page 46 P6100, P8100 & P4100 Model Group 59305, Issue 7 – March 2014
Parameter
Lower
Display
Upper
Display
Description
Default
Value
When
Visible
Decimal point
position
Decimal point position in
non-temperature ranges.
0 = XXXX
1 = XXX.X
2 = XX.XX
3 = X.XXX
=
mV, V or
mA
Control Type
Primary control
Always
Primary and Secondary
control (e.g. for heat & cool)
Primary Output
Control Action
Reverse Acting
Always
Direct Acting
Alarm 1Type
Process High Alarm
Always
Process Low Alarm
Deviation Alarm
Band Alarm
No alarm
Process High
Alarm 1 value*
Range Min. to Range Max.
Parameter repeated in Setup Mode
Range
Max.
=
Process Low
Alarm 1 value*
Range Min. to Range Max
Parameter repeated in Setup Mode
Range
Min.
=
Deviation
Alarm 1 Value*
span from setpoint
Parameter repeated in Setup Mode
=
Band Alarm 1
value*
1 LSD to full span from setpoint.
Parameter repeated in Setup Mode
=
Alarm 1
Hysteresis*
1 LSD to 100% of span (in display units)
on “safe” side of alarm point.
Parameter repeated in Setup Mode
Always
Alarm 2 Type
As for alarm 1 type
Always
Process High
Alarm 2 value*
Range Min. to Range Max.
Parameter repeated in Setup Mode
Range
Max.
=
Process Low
Alarm 2 value*
Range Min. to Range Max.
Parameter repeated in Setup Mode
Range
Min.
=
Deviation
Alarm 2 Value*
span from setpoint.
Parameter repeated in Setup Mode
=
Band Alarm 2
value*
1 LSD to full span from setpoint.
Parameter repeated in Setup Mode
=
Alarm 2
Hysteresis*
1 LSD to 100% of span (in display units)
on “safe” side of alarm point.
Parameter repeated in Setup Mode
Always
Loop Alarm
Enable
(disabled) or
(enabled)
Always