Manual

1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
59305, Issue 7 March 2014 P6100, P8100 & P4100 Model Group Page 45
Parameter
Lower
Display
Upper
Display
Description
Default
Value
When
Visible
Input type and
Range
(continued)

N type: 0 to 1399 ºC

for Europe

for USA
Always

N type: 32 to 2551 ºF

R type: 0 to 1759 ºC

R type: 32 to 3198 ºF

S type: 0 to 1762 ºC

S type: 32 to 3204 ºF

T type: -240 to 400 ºC

T type: -400 to 752 ºF
T type: -128.8 to 400.0 ºC
with decimal point
T type: -199.9 to 752.0 ºF
with decimal point

PtRh20% vs PtRh40%:
0 to 1850 ºC

PtRh20% vs PtRh40%:
32 to 3362 ºF
Input type and
Range
(Continued)


Pt100: -199 to 800 ºC

for Europe

for USA
Always

Pt100: -328 to 1472 ºF

Pt100: -128.8 to 537.7 ºC
with decimal point

Pt100: -199.9 to 999.9 ºF
with decimal point

0 to 20mA DC

4 to 20mA DC

0 to 50mV DC
 
10 to 50mV DC

0 to 5V DC

1 to 5V DC

0 to 10V DC

2 to 10V DC
Scale Range
Upper Limit

Scale Range Lower Limit +100 to Range
Max
Linear
inputs =
1000
(°C/°F
inputs =
max
range)
Always
Scale Range
Lower Limit

Range Min. to Scale range Upper Limit -
100
Linear = 0
(°C/°F =
min range)
Always