Manual

1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
Page 160 Specifications 59305, Issue 7 March 2014
17 Appendix 2 - Specification
Universal Input
General Input Specifications
Input Sample Rate:
Four samples/second.
Digital Input Filter
time constant
0.0 (OFF), 0.5 to 100.0 seconds in 0.5 second increments.
Input Resolution:
14 bits approximately.
Always four times better than display resolution.
Input Impedance:
10V DC:
47KΩ
20mA DC:
Other ranges:
Greater than 10M resistive
Isolation:
Isolated from all outputs (except SSR driver). If single relay outputs are
connected to a hazardous voltage source, and the universal input is
connected to operator accessible circuits, supplementary insulation or
input grounding is required.
PV Offset:
Adjustable input span.
PV Display:
Displays process variable up to 5% over and 5% under span.
Thermocouple
Thermocouple Ranges Available
Sensor
Type
Range Min
in C
Range Max
in C
Range Min
in F
Range Max
in F
Resolution
J (default)
-200
1200
-328
2192
J
-128.8
537.7
-199.9
999.9
0.1°
T
-240
400
-400
752
T
-128.8
400.0
-199.9
752.0
0.1°
K
-240
1373
-400
2503
K
-128.8
537.7
-199.9
999.9
0.1°
L
0
762
32
1403
L
0.0
537.7
32.0
999.9
0.1°
N
0
1399
32
2551
B
100
1824
211
3315
R
0
1759
32
3198
S
0
1762
32
3204
C
0
2320
32
4208
PtRh20%:
PtRh40%
0
1850
32
3362
Note:
Defaults to °F for USA units. Defaults to °C for non-USA units.
The Configuration Mode parameters, Scale Range Upper Limit and Scale Range Lower
Limit, can be used to restrict range.