Manual

1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
Page 152 Glossary 59305, Issue 7 March 2014
Retransmit Output 2 Scale Maximum Type: General Parameter
Defines the value of the process variable, or setpoint, at which Retransmit Output 2 will be at
its maximum value. It is similar to Retransmit Output 1 Scale Maximum.
Display code = , default value = Scale Range Upper Limit.
Also refer to Process Variable, Retransmit Output, Retransmit Output 2 Scale Minimum,
Scale Range Upper Limit and Setpoint.
Retransmit Output 2 Scale Minimum Type: General Parameter
Defines the value of the process variable, or setpoint, at which Retransmit Output 2 will be at
its minimum value. It is similar to Retransmit Output 1 Scale Minimum.
Display code = , default value = Scale Range Lower Limit.
Also refer to Process Variable, Retransmit Output, Retransmit Output 2 Scale Maximum,
Scale Range Lower Limit and Setpoint.
Retransmit Output 3 Scale Maximum Type: General Parameter
Defines the value of the process variable, or setpoint, at which Retransmit Output 3 will be at
its maximum value. It is similar to Retransmit Output 1 Scale Maximum.
Display code = , default value = Scale Range Upper Limit.
Also refer to Process Variable, Retransmit Output, Retransmit Output 3 Scale Minimum,
Scale Range Upper Limit and Setpoint.
Retransmit Output 3 Scale Minimum Type: General Parameter
Defines the value of the process variable, or setpoint, at which Retransmit Output 3 will be at
its minimum value. It is similar to Retransmit Output 1 Scale Minimum.
Display code = , default value = Scale Range Lower Limit.
Also refer to Process Variable, Retransmit Output, Retransmit Output 3 Scale Maximum,
Scale Range Lower Limit and Setpoint.
Reset Type: Controller Tuning Parameter
- Refer to Automatic Reset.
Reverse Acting Type: Controller Definition
- Refer to Direct/Reverse Action of Control Output
Scale Range Upper Limit Type: General Parameter
For linear inputs, this parameter is used to scale the process variable into engineering units.
It defines the displayed value when the process variable input is at its maximum value. It is
adjustable from -1999 to 9999 and can be set to a value less than (but not within 100 units
of) the Scale Range Lower Limit, in which case the sense of the input is reversed.
For thermocouple and RTD inputs, this parameter is used to reduce the effective range of the
input. All span related functions work from the trimmed input span. The parameter can be
adjusted within the limits of the range selected by Configuration Mode parameter . It is
adjustable to within 100 degrees of the Scale Range Lower Limit.
Display code = , default value = 1000 for linear inputs or range maximum for temperature
inputs.
Also refer to Input Span, Process Variable and Scale Range Lower Limit.