- DIN Controllers & Indicators - Product Manual
Page 104 P6010 & P8010 Model Group 59305, Issue 7 – March 2014
Parameter
Legend
for 1 sec
followed
by
Set
Value
Adjustment Range &
Description
Default
Value
When
Visible
Units
Display
(
1
/
8
Din
Only)
Display Strategy
,,,,
(see Operator Mode for details)
Always
Display Colour
Permanent Red
1/8 Din
units if
colour
change
display
fitted
Permanent Green
Red to Green if any alarm active
Green to Red if any alarm active
Comms Protocol
ASCII
=
Modbus with no parity
Modbus with Even Parity
Modbus with Odd Parity
Bit rate
.
1.2 kbps
.
=
.
2.4 kbps
.
4.8 kbps
.
9.6 kbps
.
19.2 kbps
Communica-
tions Address
A unique address for each
instrument between 1 to 255
(Modbus), or 1 to 99 (Ascii)
=
Communica-
tions Write
Enable
Read only. Comms writes
ignored
Always
Read / Write. Writing via
Comms is possible
Digital Input
Usage
Reset latched relay(s)
=
Initiate Tare (zero display)
Reset min/max PV values
Reset Alarm 1 elapsed time
Reset Alarm 1 elapsed time
& min/max PV values
Configuration
Mode Lock
Code
Always
Note:
*Linear Outputs can be configured to provide an adjustable 0.0 to 10.0VDC transmitter
power supply for external devices. This is an alternative to the fixed 24V Transmitter
Power Supply option module.