CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P127
P133 to P134
Multispeed
[ 30.00 Hz ]
Reference 4
0.01 Hz
(
99.99 Hz);
0.1 Hz
(
100.0 Hz)
P128
P133 to P134
Multispeed
[ 40.00 Hz ]
Reference 5
0.01 Hz
(
99.99 Hz);
0.1 Hz
(
100.0 Hz)
P129
P133 to P134
Multispeed
[ 50.00 Hz ]
Reference
6
0.01 Hz
(
99.99 Hz);
0.1 Hz
(
100.0 Hz)
P130
P133 to P134
Multispeed
[ 60.00 Hz ]
Reference 7
0.01 Hz
(
99.99 Hz);
0.1 Hz
(
100.0 Hz)
P131
P133 to P134
Multispeed
[ 66.00 Hz ]
Reference
8
0.01 Hz
(
99.99 Hz);
0.1 Hz
(
100.0 Hz)
The frequency reference is defined by the status of the
digital inputs programmed to multispeed as shown in
table below:
DI2 or DI5
DI3
DI4
Freq. Reference
Open
Open
Open
P124
Open
Open
0 V
P125
Open
0 V
Open
P126
Open
0 V
0 V
P127
0 V
Open
Open
P128
0 V
Open
0 V
P129
0 V
0 V
Open
P130
0 V
0 V
0 V
P131
8 speeds
4 speeds
2 speeds
Table 6.6
- Frequency reference
The multispeed function has some advantages for the
stability of the fixed preprogrammed references and the
immunityagainst electrical noises(digital referencesand
insulated digital inputs).
P128
P129
P130
P131
Output
Frequency
Acceleration
Ramp
P126
P127
Figure 6.5
- Time diagram of the multispeed function
Time
0 V
DI2 or DI5
DI3
DI4
Open
0 V
Open
0 V
Open
P124
P125
P133
0.00 to P134
Minimum
[
3.00 Hz
]
Frequency
(F
min
)
0.01 Hz
(
99.99 Hz);
0.1 Hz
(
100.0 Hz)
Define
s the maximum and minimum output frequency
(motor)
when inverter is enabled.
It is valid for any type of speed reference excepting JOG.
The parameter P133 defines a dead zone when analog
inputs are used - refer to the parameter P233 to P240.