User`s guide

91
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
P008
25 to 110
Heatsink
[ - ]
Temperature
1
o
C
Indicates the current power at the heatsink in Celsius
degrees (°C).
Theinverter overtemperature protection (E04) actswhen
heatsink temperature reaches:
P009
(1)
0.0 to 150.0
MotorTorque
[ - ]
0.1 %
Indicates the torque developed by motor in percent (%)
relating to the set rated motor torque.
The rated motor torque is defined by the parameters
P402 (rated motor speed)andP404(rated motor power).
I.e.:
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Table 6.1
- Temperature to act the overtemperature protection
P023
x.yz
Software Version
[ - ]
-
P040
0 to 6553
PID Process
[ - ]
Variable
1
(Value % x P528)
Indicates the software version installed in the DSP
memory located on the control board.
Parameter
P040, P203, P520
to
P528
are only available
from the software version V3.50 on.
Indica
tes the value of the process variable
u
sed as PID
feedback, in percent (%).
The PID function is only available from the software
version V3.50 on.
The indication unit can be changed through P528.
Refer to detailed description of the PID regulator in item
6.3.5 - Special Function Parameters.
where T
nom
isgiven in kgf.m,P
nom
isthe rated motorpower
in watts - HP - (P404), and n
nom
is the rated motor speed
in rpm - P402.
P014
00 to 41
Last Fault
[ - ]
-
Indicates the code of the last occured fault.
Item
7.1
shows a listof possible faults
,
theircode numbers
and possible causes.
T
nom
= 716 .
P
nom
n
nom
Inverter
1.6-2.6-4.0-7.0A/200-240 V
1.0-1.6-2.6-4.0A/380-480 V
7.3-10-16A/200-240V
2.7-4.3-6.5-10A/380-480 V
13-16A/380-480 V
22-28-33A/200-240 V
24-30A/380-480 V
P008 in ºC (ºF) @ E04
103 (217.4)
90 (194)
90 (194)
103 (217.4)
108 (226.4)
104 (219.2)
104 (219.2)