CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
6.2.3
Vector Control (VVC)
In V/F control, the speed regulation, that can be obtained by
setting properly slip compensation can be maintained within
1 % to 2 % of the rated speed. For instance, for a IV pole
motor/60Hz,the minimum speedvariation at no load condition
and at rated load can be maintained between 18 and 36 rpm.
Thereis still a variation of the linear V/F control: the quadratic
V/F control. This control mode is suitable for applications like
centrifugal pumps and fans (loads with quadratic torque x
speed characteristics),since it enablesa motor lossreduction,
resulting in an additional energy saving by using an inverter.
For more details about the V/F control mode, please refer to
the description of the parameters P136, P137, P138, P142
and P145.
In the sensorless vector control available at the CFW-08, the
inverter operation is optimized for the used motor, so that a
better performance in terms of torque and speed regulation
is obtained. This vector control does not require a signal of
the speed feedback through tachogenerator or encoder
coupled on motor shaft.
To maintain the magnetic flux in the motor air gap constant,
and consequently the motor torque, within the whole speed
variation range (from zero up to the field weakening point), a
sophisticated control algorithm is used that considers the
mathematic model of the induction motor.
Thus one can maintain the magnetic flux in the motor air gap
approximatelyconstant at frequenciesdown to approximately
1 Hz.
In vector control mode one can obtain a speed regulation of
0.5% (relating to the rated speed).Thus, for instance, for a IV
pole motor/60 Hz one can obtain a speed variation in the ran-
ge of 10 rpm.
Other advantage of the vector control is its easy setting
procedure. The user needs only to enter in the parameters
P399 and P407 the information about the used motor
(nameplate data) and runs the self-tuning routine (by setting
P408 = 1) and the inverter configures itself to the required
application. So the inverter is ready to be operated in an
optimized manner.
For more information,refer tothe descriptionofthe parameters
P178 and P399 to P409.