User`s guide

82
CHAPTER 5 - START-UP
Switch on the inverter.
Set P000 = 5 and P408 = 1.
Follow from now on the start-up procedures described
in item 5.3.3.
(2)
For each inverter type, the parameters P399 to P407 are
setautomatically
to the rated motor data, considering a
standard WEG motor, IV poles, 60 Hz.
When different motors are used, you must set the
parameters manually, according to the motor nameplate
data.
(3)
If the direction of rotation of the motor is notcorrect, switch
off the inverter. Wait at least 10 minutes to allowa comple-
tedischarge of thecapacitors and then swap any two wires
at the motor output.
(4)
If fault E01 occurs during deceleration,you must increase
the deceleration time at P101/P103.