User`s guide

79
CHAPTER 5 - START-UP
ACTION
HMI DISPLAY
DESCRIPTION
Use the and keys
to select the control type
Press
to save the selected
option and to start the tuning routine
after changing to VectorControl mode
Press the key and use the
keys and to set the
correct rated motor efficiency
(
in
this case
71
%)
Press the key to save the
selected option and to exit the
programming mode
Press the key to go to the
next parameter
Press the key and use the
keys and to set the
correct rated motor voltage
Press the key to save the
selected option and to exit the
programming mode
Press the key to go to the
next parameter
Press the key and use the
keys and to set the
correct rated motor current (in this
case 2.90 A)
Press key to save the
selected option and to exit the
programming mode
Press the to go to the next
parameter
Press the key and use the
keys and to set the
correct motor speed (in this case
1720 rpm)
Press the key to save the
selected option and exit the
programming mode
Press the key to go to the
next parameter
P202 = 2: Vector
Motor efficiency:
50 to 99.9 %
Set motor efficiency:
71 %
Exit the programming mode
Rated motor voltage range:
0 to 600 V
Set rated motor voltage:
220 V (the default valueis maintained)
(2)
Exit the programming mode
Rated motor current range:
0.3 x I
nom
to 1.3 x I
nom
Set rated motor current: 2.90 A
Exit the programming mode
Rated motor rpm range:
0 to 9999 rpm
Programmed rated motor rpm:
1720 rpm
Exit the programming mode
Rated motor frequency:
0 to F
max