CHAPTER 5 - START-UP
5.3.2
Start-up -
Operation via Terminals -
Control Mode:
Linear V/F (P202 = 0)
Connections are according to figures 3.6 and 3.16.
ACTION
HMI DISPLAY
DESCRIPTION
Refer to figure 3.16
Switch
S1 (
FWD / REV
)
=
open
Switch S2 (Reset) = open
Switch S3 (Start/Stop) = open
Poten
tiometer
R1 (Ref.)
=
totally CCW
Power-up inverter
Press the key.
This procedure is not necessarywhen
inverters were delivereddummypanel,
since it will be automatically in remote
mode
Close
S3
– Start/Stop
Turn potentiometer totally CW
Close
S1
– FWD / REV
Open
S3
– Start / Stop
Inverter is ready to be operated
L
ocal LED
switches OFF and remote
LED switches ON
.
Control and
Reference are switched to remote
(via
terminals
)
Note:
To maintain inverter permanently
in remote mode, set
P220
=
1.
If the inverter is switched off and
afterwards switched on, it
will
now operate in local mode
because P220 = 2 (factory
setting). This setting means
that the local/remote selection
source is via keypad and the
default mode (that is the mode
when the inverter is switched
on) is local. For further
information refer to the
description of P220 in chapter 6
Motor accelerates from 0 Hz to 3 Hz
(*)
(minimum frequency), CW direction
(1)
The frequency reference is given by the
potentiometer R1
Motor accelerates up to the maximum
frequency (P134 = 66 Hz)
(2)
Motor decelerates
(3)
down to 0 rpm (0
Hz), reverses the direction of rotation
(FWD/REV) accelerating back up to the
maximum frequency (P134 = 66 Hz)
Motor decelerates
(3)
down to 0 rpm
NOTES!
(1)
If the direction of rotation of the motoris not correct, switch
off the inverter. Wait 10 minutes to allow a complete
capacitor discharge and swap any two wires at the motor
output
.
(2)
If the acceleration current becomes too high, mainlyat low
frequencies, set the torque boost (IxR Compensation) at
P136.
(*)
90 rpm for 4-pole motor.