User`s guide

72
CHAPTER 4 - KEYPAD (HMI) OPERATION
(3)
If the last programmed value in the parameter is not
functionallycompatible withotherparameter values already
programmed, E24 = ProgrammingError, will be displayed.
Example of programming error:
Programming of two digital inputs (DI) with the same
function. Refer to table 4.1 for list of programming errors
that can generate an E24 Programming Error.
(4)
To allowthe reprogramming ofanyparametervalue (except
for P000 and P121) it is required to set P000 = 5.
Otherwise you can onlyread theparameter values,but not
reprogram them
.
For more details, refer to the parameter
P000 description in chapter 6.
NOTE!
(1)
For parametersthat canbe changed with themotorrunning,
the inverter will use the new value immediatelyafter it has
been set. For parameters that can be changed only with
motor stopped, the inverter will use this newvalue onlyafter
the key is pressed.
(2)
By pressing the key after the reprogramming, the
new programmed value will be stored automatically and
will remain stored until a new value is programmed.