User`s guide

71
CHAPTER 4 - KEYPAD (HMI) OPERATION
4.2.4
Parameter Viewing and
Programming
All CFW-08 settings are made through parameters. The
parameter are shown on the display by the letter
P
followed
bya number:
Example (P101):
101 = Parameter Number
Each parameter is associated with a numerical value
(parameter value), that corresponds to the selected option
among the available ones for this parameter.
The parameter values define the inverter programming or the
value of a variable (e.g.: current, frequency, voltage).For in-
verter programming you should change the parameter
content(s).
It is necessary to set P000 = 5 before to change a parameter
value. Otherwise you can only read the parametervalues, but
not reprogram them
.
For more details, refer to the parameter
P000 description in chapter 6.
ACTION
HMI DISPLAY
DESCRIPTION
TurnON the inverter
Press the key
Use the keys
and
Press the key
Use the keys
and
Press the key
Inverter is ready to be started
Select the desired parameter
Numerical value associated with the
parameter
(4)
Set the new desired value
(1) (4)
(1) (2) (3)
ParametersP002 to P099 are reserved for the displayof read-
onlyvalues.
The factorydefault displaywhenpower isapplied to the inverter
is P002 (frequency proportional value in V/F control mode
(P202 = 0 or 1) and motor speedin rpm in vector control mode
(P202 = 2)).
ParameterP205 defines the initial monitoring parameter, i.e.,
defines the read-onlyvariable that will be displayed when the
inverter is powered up. For further information refer to P205
description in chapter 6.
4.2.3
Read-Only Parameters