User`s guide
52
CHAPTER 3 - INSTALLATION
AND CONNECTION
3.3.2
Emissionand Immunity
Levels Description
4) The length of the wiring between filter and inverter must be
kept as short as possible.
5) The cables shielding
(motor and control)
must be solidly
connected to thecommonback plate,using a metal bracket.
6)Grounding asrecommended in thismanual.
7)Useshort
earthing cabletoearththe externalfilterorinverter.
When an external filter is used, only use an earth cable at
filterinput-theinverterearthconnectionisdonebythemetallic
back plate.
8)Earth the backplate using a braid, as shortas possible. Flat
conductors (e.g. braidsor brackets) have lower impedance
athighfrequencies.
9)Use cable glands wheneverpossible.
EMC Phenomenon
Emission:
Conducted Emission (Mains Terminal
Disturbance Voltage - Frequency Band
150 kHz to 30 MHz)
Radiated Emission (Electromagnetic
Radiation Disturbance - Frequency
Band 30 MHz to 1000 MHz)
Immunity:
Electrostatic Discharge (ESD)
Fast Transient-burst
Conducted Radio-frequency
CommonMode
Surge
Radio-frequency Electromagnetic Field
Basic Standard
for Test Method
IEC/EN61800-3
IEC 61000-4-2
IEC 61000-4-4
IEC 61000-4-6
IEC 61000-4-5
IEC 61000-4-3
Level
“First environment”
(1)
unrestricted distribution
(3)
Category C1
, or;
“First environment”
(1)
restricted distribution
(4) (5)
Category C2, or;
“Second environment”
(2)
unrestricted distribution
(3) (6)
Category C3
“First environment”
(1)
, restricted distribution
(4) (5)
“Second environment”
(2)
, unrestricted distribution
(3)
6 kV contact discharge
4 kV/2.5 kHz (capacitive clamp) input cable
2 kV/5 kHz control cables; 2 kV/5 kHz (capacitive
clamp) motor cable; 1 kV/5 kHz (capacitive clamp)
external keypad cable
0.15 to 80 MHz; 10 V; 80 % AM (1 kHz) - motor,
control and remote keypad cable 1.2/50
s, 8/20
s
1 kV coupling line to line
2 kV coupling line to earth
80 to 1000 MHz; 10 V/m; 80 % AM (1 kHz)
Table 3.7
- Specification of the emission and immunity levels