User`s guide
50
CHAPTER 3 - INSTALLATION
AND CONNECTION
NOTES!
S1
and
S2
are push buttons, start (NO contact) and stop
(NC
conta
ct),respectively.
The speed reference can be via analog input AI1 (as in
Connection2), viakeypad (HMI-CFW08-P),or via any other
source (as described in the parameters P221 and P222).
When a line fault occurs by using this connection with the
motor running and the S1 and S2 switches are in original
position (S1 openned and S2 closed), at the moment the
voltagereturns the inverterwillnot beenabled automatically,
it will only be enabled if the S1 switch were closed again (a
pulse at the Start digital input).
The Start/Stop function is described in chapter 6.
Connection 4 - FWD/REV Function
Parameter to be programmed:
Set DI1 to Forward Run : P263 = 8
Set DI2 to Reverse Run: P264 = 8
Make sure the inverter commands are via terminals, i.e.,
P229 = 1
to local mode or P230 = 1 to remote mode.
The figure 3.18 below shows the inverter terminal connection
for this type of driving.
Figure 3.18
- XC1 wiring for connection 4
S1 open: Stop
S1 closed: Forward Run
S2 open: Stop
S2 closed: Reverse Run
DI1 - Forward Run
DI2- Reverse Run
DI3 - Reset
COM
AI1
+10 V
AI2
AO1
NC
Common
NO
DI4 - No Function
S2
S1
1
2
3
4
5
6
7
8
9
10
11
12
NOTE!
For the correct operation of the connection 4, P266 must
be programmed as “Not Used”.
The speed reference can be via analog input AI1 (as in
connection 2),via keypad (HMI-CFW08-P), or via anyother
source (refer to the description of parameters P221 and
P222).
When a line fault occurs, this connection with switch S1 or
switch S2 isclosed, the motor will be enabled automatically
as soon as the line is re-established.