User`s guide

204
TECHNICALSPECIFICATIONS
This chapter describes the technical specifications (electrical
and mechanical) of the CFW-08 inverter series.
9.1
POWER DATA
AC Input Specifications:
Voltage: + 10 %, -15 % (with loss of motor efficiency)
Frequency: 50/60 Hz 2 Hz)
Phase unbalance:
3 %
Overvoltage: Category III (EN 61010/UL 508C)
Transient voltages according to CategoryIII.
Minimum line impedance: variable according to inverter
model.
Refer to item 8.21.
Power-up:
maximum 10 ON/OFF cycles per hour (1 every 6
minutes).
CHAPTER 9
1.6/
200-240
0.6
1.6
2.4
3.5
5
0.25 HP/
0.18 kW
No
No
Yes
Yes
18
2.6/
200-240
1.0
2.6
3.9
5.7
5
0.5 HP/
0.37 kW
No
No
Yes
Yes
30
4.0/
200-240
1.5
4.0
6.0
8.8
5
1 HP/
0.75 kW
No
No
Yes
Yes
45
7.0/
200-240
2.7
7.0
10.5
8.1
5
2 HP/
1.5 kW
No
No
No
No
80
151 x 75 x 131
[5.94 x 2.95 x 5.16]
Single-phase
Three-
phase
1.6/
200-240
0.6
1.6
2.4
2.0/3.5
(4)
5
0.25 HP/
0.18 kW
No
No
Yes
Yes
18
2.6/
200-240
1.0
2.6
3.9
3.1/5.7
(4)
5
0.5 HP/
0.37 kW
No
No
Yes
Yes
30
4.0/
200-240
1.5
4.0
6.0
4.8/8.8
(4)
5
1 HP/
0.75 kW
No
No
Yes
Yes
44
Single-phase or
three-phase
Model: Current (A) / Voltage (V)
Power (kVA)
(1)
Rated output current (A)
(2)
Max. output current (A)
(3)
Power supply
Rated input current (A)
Switching frequency(kHz)
Maximum motor power
(5)
Dynamic braking
Internal CategoryC2
RFI filter (optional)
Footprint Category C2 RFI filter
(optional)
External Category C1 RFI filter
(optional)
Watt loss (W)
Dimensions in mm [in]
(Height x Width x Depth)
9.1.1
200-240 V Power Supply
Table 9.1 a)
- Technical information about the inverter models 1.6-2.6-4.0-7.0 A/200-240 V