User`s guide
187
CHAPTER 8 - CFW-08 OPTIONS AND ACCESSORIES
Figure 8.32
- CFW-08 network connection through RS-485 serial interface
Network
Master
(PC, PLC)
RS-485
CFW-08
Cable
Shielding
A B
RS-485
XC29
A B
RS-485
XC29
CFW-08
CFW-08
KRS-485-CFW08
NOTE!
The wiring of the RS-232 must be laid separately from the
power cables and the control wiring in 110 V/220 V.
NOTE!
You can not use RS-232 and RS-485 simultaneously.
6
5
4
1
2
3
TX
0 V
RX
+5 V
RTS
0 V
Figure 8.33
- Description of the XC8 (RJ-6) connector
Notes:
Line termination: connect the termination resistors at the
ends of the line.
Grounding of the cable shield: connectthe shielding to the
equipment frame (suitable grounding);
Recommended cable: for balanced shielding.
Ex.:AFS series, manufacturer KMP.
Figure below shows the pin position of the XC8 connector of
the KCS-CFW08-S module.
8.24.7
Physical
Connection
RS-232 and RS-485