CHAPTER 8 - CFW-08 OPTIONS AND ACCESSORIES
BYTE LOW:
logical level of the desired action.
CL0:
1 = enabling (run)
0 = disabling by ramp (stop)
CL1:
1 = enabling
0 = general disabling (stops by inertia)
CL2:
1 = forward
0 = reverse
CL3:
1 = JOG active
0 = JOG inactive
CL4:
1 = remote
0 = local
CL5:
not used
CL6:
not used
CL7:
the transition in this bit from 0 to 1 causes the inverter
“RESET” when any error condition is present
Notes:
Disabling via DIx has priority over these disabling.
To disable the inverter via serial interface, set CL0 = CL1 =
CL8 = CL9 = 1, while the external disabling (example, via
DI) must be inactive.
If CL1 = 0 and CL9 = 1, it will occur general disabling.
If CL0= 0 and CL8 = 1, theinverter will be disabledbyramp.
V04 (code 00704)
Frequency reference given by the Serial interface
(reading/writing variable):
Allows to send the frequency reference to the inverter, when
P221 = 5 in local mode and P222 = 5 in remote mode. The
variable resolution is shown in the item 8.24.3.2.
V05 (code 00705)
Enabled controls to the Serial interface (reading
variable):
CL7
CL6
CL5
CL4
CL3
CL2
CL1
CL0
MSB
LSB
CHSH
CHSL
CHSL
CHSL
CHSL
CHSL
CHSL
CHSL
CHSL
0
7
6
5
4
3
2
1
0
MSB
LSB