User`s guide
156
CHAPTER 8 - CFW-08 OPTIONS AND ACCESSORIES
8.11
KCS-CFW08
Serial communication module RS-232: is inserted in the place
of the parallel keypad, enabling the RS-232 connection
(connector RJ-6).
The RS-232 serial interface enables the point-to-point
connection (inverter - master). It is gavanically isolated and
enables the use of interconnectingcables in lengthsupto10 m
(32.8 ft)
.
Through the RS-232 serial interface you can control, set
parameters and monitor the CFW-08. The communication
protocol is based on the communication byenquiry/response
(master/slave),accordingto ISO1745,ISO646, with character
exchange of typeASCII between the inverter (slave) and the
master. The Master can be a PLC, a PC, etc. The maximum
transfer rate is 38400 bps.
For the RS-485 serial communication, both point-to-point (an
inverter and a master) or multipoint (up to 30 inverters and
one master), you can connectthe KCS-CFW08 module to an
KRS-485-CFW08module - for moredetails, refer toitem 8.13.
43
[1.69]
21
[0.83]
57
[2.24]
Figure 8.15
- Dimensions in mm [in] of the RS-232 serial
communication module KCS-CFW08 and RJ (XC8) signal connector
20
[0.79]