CHAPTER 8 - CFW-08 OPTIONS AND ACCESSORIES
8.6.2
HMI-CFW08-RS
Start-up
After installation (including interconnecting cable), power-up
the inverter.
HMI-CFW08-RS must display
The inverter programming via HMI-CFW08-RS is exactly the
same as the inverter programming via HMI-CFW08-P (for
more details about the programming, refer to chapter 4).
To enable all the keys of the HMI-CFW08-RS and thus
make
it equivalent to HMI-CFW08-P both for programming
and operation, set the following parameters:
8.6.1
HMI-CFW08-RS
Installation
The remote serial keypad (HMI-CFW08-RS) can be installed
in the cabinet door (doorthickness between 1 and 3 mm [0.04
and 0.12 in]), as presented in the following figures.
Figure 8.9
- Installation of the HMI-CFW08-RS
Function viaHMI-CFW08-RS
Frequencyreference
Commands
(*)
Forward/Reverse Selection
Local/Remote Selection
Local Mode
P221 = 0
P229 = 2
Remote Mode
P222 = 0
P230 = 2
P231 = 2
P220 = 5 (default local) or
P220 = 6 (default remote)
Note:
Factory Setting
(*)
Excepttheforward/reverse selection thatalso depends on the parameter
P231.
Table 8.2
- Parameter setting for HMI-CFW08-RS operation
NOTE!
Due to the internal processing time of CFW-08 it is not
possible touse the external serial keypad, with theswitching
frequency set to 15 kHz (P297 = 7).
This optional is not compatible with the version “A3” and
“A4” of the control board. Refer to item 2.4 for further
information on these control boards.
52 mm
(2.05 in)
92 mm
(3.62 in)
Max. 3 mm
(0.12 in)