User`s guide
140
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
P536
0 or 1
Automatic Setting
[ 0
]
of P525
-
It is possible to enable/disable the copy of P040 (PID
process variable)
in P525 whenthe changing from ma-
nual to automatic mode using parameter P536, that is
described below.
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P536
0
1
Function
Active (copies the value of P040 in P525)
Inactive (does not copies the value of P040 in P525)
Table 6.33
- Configuration of P536
If the action of the PID regulator is reverse (P527 = 1),
the condition for the CFW-08 to leave the “Sleep Mode”
is defined by P212, and by the PID regulator error must
be lower than the P535 value, therefore:
FE
P212
Srdy
erro
PID
-P535
run
t
P213
Being:
FE
- Frequency at the ramp input (frequency reference);
Erro
PID
- The PID setpoint (P525 orAI2) subtracted from
the process variable (P040);
t
- Elapsed time interval;
Srdy
-Active “Sleep Mode” Indication;
run
- Enabled inverter Indication.