User`s guide
138
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P520
0.000 to 7.999
PID Proportional
[ 1.000 ]
Gain
0.001
P521
0.000 to 9.999
PID Integral
[ 1.000
]
Gain
0.001
P522
0.000 to 9.999
PID Differential
[ 0.000
]
Gain
0.001
The integral gain can be defined as being the time
required to change thePI regulator outputfrom0 to P134,
that is given, in seconds, by the equation below:
For the following conditions:
-
P040 = P520 = 0.
-
DI3 in automatic position.
P525
0.00 to 100.0
Setpoint (via
[ 0.00
]
Keypad) of the
0.01 %
PID Regulator
Provides the setpoint (reference) of the process via
cointrol via the and keys for the PID regulator,
provided that P221 = 0 (local) or P222 = 0 (remote) has
been set to automatic mode. If it has been set to Manual
Mode, the frequency reference is given by P121.
If P120 = 1 (backup active), the value of P525 is
maintained at the lastset value (backup), evenwhen the
inverter is disabled or turned off.
P526
0.01 to 10.00
Process Variable
[ 0.10 s ]
Filter
0.01 s
It sets the time constant of the Process Variable Filter.
It is useful for noise filtering at the analog inputAI1
(feedback of the process variable).
P527
0 or 1
PIDAction
[ 0
]
-
Defines the action type of the PID regulator.
Select it according to the table below:
t =
16
P521
.
P525
P527
0
1
Action Type
Direct
Reverse
For this the
motor speed
must
Increase
Increase
Process
variable
requirement
Increase
Decrease
P527 to be
used
0 (Direct)
1 (Reverse)
Table 6.31
- Configuration of the action type of the PID regulator
Table 6.32
- Description of the options operations for P527










