User`s guide

137
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Figure 6.28
- Application example of an inverter with PID regulator
CFW-08
P525
Content
Setpoint can
be changed
by the keys
X1
1
2
3
4
5
6
Line
3
4
S1
OFF ON
1
2
3
4
5
6
7
8
9
10
11
12
DI1 - Gen. Enable
DI3- Manual/Auto
DI4 - Start/Stop
AI1 - Feedback
Pressure
Transducer
4-20 mA
0-25 bar
0-100 %
(0-25bar)
5k
Setpoint viaAI2(available
with CFW-08 Plus only)
P222 = 2
P238 = 1.00
P239 = 0
P240 = 0.00
Remote mode operation (P220 = 1).
Setpoint via keypad.
Inverter Parameterization:
P220 = 1
P520 = 1.000
P222 = 0
P521 = 1.000
P234 = 1.00
P522 = 0.000
P235 = 1
P525 = 0
P238 = 0.00
P526 = 0.1s
P203 = 1
P527 = 0
P205 = 6
P528 = 25
Process