CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Example: consider the data of the last example (pressure
sensor of 0-25bar and P234 = 2.00) . P528 must be set to
25/2 = 12.5.
Theparameter P040 can be selected as the displaydefault
parameter P205 = 6.
P528 =
full scale value of the used sensor
P234
The parameter P040 indicates the value of the process
variable (feedback) in the scale selected at P528, that is
set according to the following equation: