CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
[Factory Setting]
Parameter
Unit
Description / Notes
TheAI1’term is theAI1 analog input value after gain and
offset have been applied.
For factory default setting, the local reference is via the
and keys of the keypad and the remote
reference is via analog inputAI1.
The reference value set by the and keys is
contained in parameter P121.
For details of theElectronicPotentiometer (EP)operation,
refer to figure 6.20.
When option 4 (EP) is selected, set P265 and P266 to 5.
When option 6 (multispeed) is selected, set P264 and/
or P265 and/or P266 to 7.
For more details, refer to items 6.2.4 and 6.2.6.
Table 6.14
- Programming P221 (local mode) or P222 (remote
mode) for speed reference selection
P221
(3)
0 to 8
Frequency
[ 0 ]
Local Reference
-
Selection
P222
(3)
0 to 8
Frequency
[ 1 ]
Remote
-
Reference
Selection
Defines the frequency reference selection in the Local and
Remote
mode.
P221/P222
0
1
2 or 3
4
5
6
7
8
Reference Source
Keys and of the HMIs (P121)
Analog input AI1' (P234, P235 and P236)
Analog input AI2' (P238, P239 and P240)
Electronic potentiometer (EP)
Serial
Multispeed (P124 to P131)
Sumof the analoginputs (AI1'+AI2') 0 (negative
values are zeroed)
Sum of the analog inputs (AI1'+AI2')
The direction of rotation is the only operation control that
depends on other parameter for operation refer to the
parameter P231.
For more details, refer to items 6.2.4, 6.2.5 and 6.2.6.
P229
(3)
0 to 2
Local Command
[ 0 ]
Selection
-
P230
(3)
0 to 2
Remote
[ 1 ]
Command
-
Selection
Define the control sources for the inverter enabling and
disabling FWD/REV and JOG.
Table 6.15
- Programming P229 and P230 for
origin selection of the inverter commands
P229/P230
0
1
2
Control Source
HMI-CFW08-P or HMI-CFW08-RP Keypad
Terminals (XC1)
HMI-CFW08-RS keypad
or serial interface