User`s guide

106
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P215
(3) (4)
0 to 2
Keypad Copy
[ 0
]
Function
-
The keypad copy function is used to transfer the content
of the parameters from one inverter to another.
P215
0
1
2
Notes
-
Transfers the current parameter values
of the inverter to non volatile memory
(EEPROM) of the HMI-CFW08-RS
keypad. The current inverterparameters
are not changed
Transfers thecontent of the non volatile
memoryof the HMI-CFW08-RSkeypad
(EEPROM) to the current inverter
parameters
Action
No Function
Procedure is as follows:
1.
Connectthe keypad (HMI-CFW08-RS)to the inverter
from which the parameters will be copied (inverterA -
source inverter).
2. Set P215 = 1 (copy) to transfer the parameter values
from the inverter A to the keypad. Press key.
During running of the Copyfunction,display will show
.
P2
15
resets automatically to
0 (
Off
)
after transfer has been completed.
3.
Disconnect the keypad from the inverter (A).
4.
Con
n
ect the same keypad to the inverter to which
the
parameters will be transferred (
i
nverter B - target
inverter).
5.
Set P215 = 2 (paste) to transferthe content of the non
volatile memory of the keypad (EEPROM - has the
inverterAparameters) to inverterB. Press the key.
While the keypad is running the paste function, the
displayshows
,
anabbreviationforpaste.
When P215 returns to 0, the parameter transfer has
been concluded. Now inverters
A
and
B
will have the
same parameter values.
Copy
(inverter

keypad)
Paste
(keypad

inverter)
Table 6.11
- Programming P215 for Copy function execution