User`s guide
104
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
P205
0
1
2
3
4 and 5
6
Read Parameter
P005 [Output Frequency (Motor)]
P003 [Output Current (Motor)]
P002 (Value Proportional to Frequency)
P007 [Output Voltage (Motor)]
Not Used
P040 (PID Process Variable)
In the event of a fault trip, except for E14, E24 and E41,
the inverter can initiate an automatic resetafter the time
given by P206 is elapsed.
If P206
2 auto-reset does not occur.
If after auto-reset the same fault is repeated three times
consecutively, the auto-reset function will be disabled.A
faultis considered consecutive if it happens againwithin
30 seconds after the auto-reset. Thus if a fault occurrs
four times consecutively, this fault remains indicated
permanently(and inverter disabled).
P206
0 to 255
Auto-Reset Time
[
0
]
1 s
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Programs all parameters to the standard factory default,
when P204 = 5.
The parameters P142 (maximum output voltage), P145
(field weakening frequency), P295 (rated current),P308
(inverter address) and P399 to P407 (motor parameters)
are notchanged when the factorydefaultparameters are
loaded through P204 = 5.
When P204is set to5 with the version “A2”of the control
board, it is necessary to set P234 and P238 to 2 as well
as P236 and P240 to -50 % so that the analog inputs
can be bipolar (-10 to +10) Vdc.
Selects which of the parameters listed below will be
shown on the display as a default after the inverter has
been powered up.
P205
0 to 6
Display
[ 2
]
Default
-
Selection
P204
(3)
0 to 5
Load Factory
[ 0 ]
Setting
-
It allows that the read-onlyparameterP002 indicates the
motor speed in value, for instance, rpm.
The indication of P002 is equal to the output frequency
value (P005) multiplied by the value of P208, i.e.,
P002 = P208 x P005.
If desired, the conversion from Hz to rpm is made as a
functionof the pole number:
P208
0.00 to 99.9
Reference Scale
[ 1.00 ]
Factor
0.01 (
9.99)
0.1 (
10.0)
Table 6.9
- Configuration of P205