CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Selects or not the special function of the PID Regulator.
P203
(3)
0 or 1
Special Function
[ 0 ]
Selection
-
P203
0
1
Special Function
None
PID Regulator
Refer to detailed description of PID Regulator
parameters (P520 to P528).
When
P203
is changed to
1, P265
is changed
automaticallyto 15 (DI3 = manual/automatic).
Thevector control allows a better performance regarding
to torque and speed control. The CFW-08 vector control
operateswithout motorspeed sensor(sensorless).Itmust
be applied whenfollowing performances arerequired:
- Better dynamics (faster accelerations and stoppings).
-
When more accurate speed control is required.
- When hightorques at lowspeeds are required (
5 Hz).
Ex
a
mpl
e
s:
in positioning, such as load moving, packing
machines, dosing machines, etc.
The vector control can not be used in multimotor
applications.
The performance of the vector control with a switching
frequency of 10 kHz is not so good as when a switching
frequencyof 5 kHz or 2.5 kHz is used. It is not possible to
usea vector control witha switching frequencyof 15kHz.
For more details about the vector control, refer to item
6.2.3.
Figure 6.15 b)
-V/F control modes (scalar)
Output Voltage
P136 = 0
P142
0
P145
Output
Frequency
b) Quadratic V/F
Vector control modes:
Table 6.8
- Configuration of P203 for using or not the special
function PID Regulator