Operating instructions
VENTILATOR HOOD 
HOOD SECTION - VACUUM SYSTEM 
11 
SV504 SvcManual WV-4H(RW) 
SWITCH FUNCTION 
VS1  PRE-FILTER POSITION MONITOR 
    Unit will not function unless a pre-filter 
    is properly installed, as sensed by the 
    pressure drop across it. Pressure drop 
    across the pre-filter must exceed setting 
    before cooking appliance is energized. 
    Insufficient pressure drop will illuminate 
 "CHECK FILTER" indicator. 
VS2  FILTER PACK ALERT 
 Will illuminate "REPLACE FILTER PACK" 
    indicator if pressure drop across the filter 
 pack exceeds setting. 
VS3 PRE-FILTER ALERT 
 Will illuminate "REPLACE PRE-FILTER" 
 indicator if pressure drop across the pre- 
 filter exceeds setting. 
VS4  AIR FLOW MONITOR 
    Pressure drop must exceed setting before 
    cooking appliance is energized. As filters 
    become plugged, airflow decreases. 
    Beyond the useful life of the filters, air flow 
    will be insufficient to maintain the required 
 pressure drop, which will shut-down 
    ventilator fan and cooking appliance and 
 illuminate "SERVICE REQUIRED" 
 indicator. 
IMPORTANT: 
Vacuum switch settings are factory set, and are not 
adjustable. 
PLENUM PORT
(AFTER FILTER PACK)
CABINET PORT
(BEFORE FILTER PACK)
FAN
PORT A
PORT B
PORT B
PORT C
PORT C
PORT C
PORT A
VS1
VS2
VS4
VS3
FAN
GREASE
BAFFLE
PRE-
FILTER
FILTER
PACK
FAN
AMBIENT
PRESSURE
PRESSURE
DROP ACROSS
BAFFLE
PRESSURE
DROP ACROSS
PRE-FILTER
PRESSURE
DROP ACROSS
FILTER PACK
PRESSURE
RISE FROM
FAN
AIR FLOW
SWITCH
VS1
SWITCH
VS2
SWITCH
VS4
SWITCH
VS3