Installation manual

4 Magnitude™ Frictionless Centrifugal Chillers Model WMC IM 1029-2
Installation
Receiving and Handling
The unit should be inspected immediately after receipt for possible damage.
All Daikin centrifugal water chillers are shipped FOB factory and all claims for handling and shipping
damage are the responsibility of the consignee.
On units with factory-installed insulation, the insulation is removed from the vessel lifting hole (also used for
transportation tie-downs) locations and are shipped loose. They should be secured in place after the unit is
finally placed. Neoprene vibration pads are also shipped loose in a control panel.
If so equipped, leave the shipping skid in place until the unit is in its final position. This will aid in handling
the equipment.
Extreme care must be used when rigging the unit to prevent damage to the control panels and refrigerant
piping. See the certified dimension drawings included in the job submittal for the center of gravity of the unit.
If the drawings are not available, consult the local Daikin sales office for assistance.
T
he unit can be lifted by fastening the rigging hooks to the four corners of the unit where the rigging eyes are
located (see Figure 1). A spreader bar must be used between the rigging lines to prevent damage to the
control panels, piping and electrical panels. The spreader-bar length should be equal to, or no more then 1-
foot shorter than the distance between the lifting holes located at opposite ends of the chiller. The unit will
require a single spreader-bar of this length capable of supporting 1.5 times the shipping weight of the unit.
Separately, all cables and hooks by themselves must also be capable of supporting 1.5 times the shipping
weight of the unit.
Figure 1, WMC, Major Component Locations
Compressor #2
Control Panel
Operator Interface
Touch Screen, OITS
Rigging Holes
Each Corner
Evaporator
Condenser
Condenser
Relief Valves
Behind Panel
Evap. Relief Valve
(Behind Panel)
Combined Discharge
Check and Shutoff Valve
Power Panel
Inlet
Outlet
Compressor #1
Electronic Expansion Valve
Suction Shutoff Valve