Installation manual

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers Model WMC 29
Figure 24, Case 8 WMC 145S Field Power Wiring
NOTES:
1. Not applicable
2. Remove standard line reactor when optional combination line reactor/harmonic filter assembly is used.
3. Circuit breakers shown in the diagram function exclusively as disconnect switches.
Case 9 WMC 145S Field Power Wiring
Case 9 adds a factory-mounted EMI to the remote-mounted harmonic filter. The field wiring remains the same
as Case 8 except that the wiring out to the filter emanates from the EMI rather than the disconnect switch as in
Case 8.