Operating instructions

6
INTERFACING TO A BCP-4 OUTDOOR RESET CONTROL
The BCP-4 is a commercial outdoor reset control for heat which can directly control
up to four output stages.
The BCP-6/12 can be used to expand the number of output stages of this control
from 4 to 6 or 12. Check the I/O manual for the BCP-4 to be sure it is set up correctly
to interface to the BCP-6/12.
When being used in the interface mode, the BCP-6/12 does not require a sensor. It
receives its staging information from the BCP-4 (see pg. 17).
Dip switches 6 and 7 must be ON and dip switch 8 must be OFF for the BCP-6/12 to
recognize the staging information.
Terminal 12 of the BCP-4 must be wired to BCP-6/12 input terminal 4.
Terminal 13 of the BCP-4 must be wired to BCP-6/12 input terminal 5.
Terminal 14 of the BCP-4 must be wired to BCP-6/12 input terminal 1.
Terminal 15 of the BCP-4 must be wired to BCP-6/12 input terminal 2.
Terminal 15 and 16 of the BCP-4 must be jumped together.
Terminal 17 of the BCP-4 must be wired to BCP-6/12 input terminal 11.
WIRING THE OUTPUT STAGES
Check all the relays are firmly seated in their sockets.
Any output stage which is not used or does not have a relay must have its OFF/
AUTO/ON switch in the OFF position.
Each output stage has one Normally Open (N.O.) relay contact.
The N.O. contacts are dry contacts only. They do not source any voltage.
Each N.O. contact is capable of switching 6A resistive at 120VAC.
Total output of all stages must not exceed 15A.
ON/OFF Units
(Refer to Chart Below)
Each unit has one relay and one OUTPUT associated with it.
Wire the N.O. relay contacts in series with the unit’s limit circuit.
F
or non-active
stages
For stages which
are to be part of
the automatic
sequence
STAGE 1
OFF
AUTO
ON
OUTPUT Number of ON/OFF Boiler Units
1 2 3 4 5 6 7 8 9 10 11 12
Output
1
Unit 1 Unit 1 Unit 1 Unit 1 Unit 1 Unit 1 Unit 1 Unit 1 Unit 1 Unit 1 Unit 1 Unit 1
Output
2
Unit 2 Unit 2 Unit 2 Unit 2 Unit 2 Unit 2 Unit 2 Unit 2 Unit 2 Unit 2 Unit 2
Output
3
Unit 3 Unit 3 Unit 3 Unit 3 Unit 3 Unit 3 Unit 3 Unit 3 Unit 3 Unit 3
Output
4
Unit 4 Unit 4 Unit 4 Unit 4 Unit 4 Unit 4 Unit 4 Unit 4 Unit 4
Output
5
Unit 5 Unit 5 Unit 5 Unit 5 Unit 5 Unit 5 Unit 5 Unit 5
Output
6
Unit 6 Unit 6 Unit 6 Unit 6 Unit 6 Unit 6 Unit 6
Output
7
Unit 7 Unit 7 Unit 7 Unit 7 Unit 7 Unit 7
Output
8
Unit 8 Unit 8 Unit 8 Unit 8 Unit 8
Outpu
t 9
Unit 9 Unit 9 Unit 9 Unit 9
Output
10
Unit 10 Unit 10 Unit 10
Output
11
Unit 11 Unit 11
Output
12
Unit 12
System
* * * * * * * * * * * *
NO
C
Unit
Output
Limit
Circuit
Typical Limit Circuit for
ON/OFF Units
Refer to Specific Boiler Wiring Diagram
INPUTS
3
4
567
8
9
10
11
Shield
+
Sensor Com Dry Contact Only Dry Contact Only
TEMP
HEAT
DEMAND
DHW
PRESSURE
4-20mA
O
U
D
OO
9
10 11 12
13
14
15
16
17
12
Sensor Com
BCP-6/12 Input Terminals
BCP-4 Output Terminals
* System relay should always be installed.