Install Instructions
®
Series 3 WATER BOILER — Boiler Manual
Connect breeching (continued)
Figure 5 Breech connection, typical, for gravity venting into chimney
Chimney venting (continued)
Connect breeching:
Long horizontal breechings, excessive
number of tees and elbows or other ob-
structions restricting combustion gas fl ow
can result in possibility of condensation,
fl ue gas leakage and carbon monoxide
emissions, which can lead to severe per-
sonal injury or death.
1. Connect full-sized breeching when possible. See
Table 2, page 12, and Figure 5, below.
2. Connection must be made above bottom of chimney
to avoid blockage. Breeching must not enter chim-
ney far enough to cause obstruction. Use thimble or
slip joint where breeching enters chimney to allow
removal for cleaning.
3. When burner and boiler are properly installed,
breeching draft will be approximately -0.01” to
-0.02” W.C. Install barometric control in breech-
ing, per control manufacturer’s instructions, when
excess draft needs to be relieved or to comply with
applicable codes and regulations. Use draft gauge to
adjust proper opening.
The Ultra Oil boiler is capable of being
pressure fi red. Overfi re pressure may be
positive even with a negative pressure
in the chimney. See the Ratings table on
page 39 for boiler draft loss.
The pressure in the breeching and chim-
ney must always be negative unless the
chimney and breeching are constructed
of vent piping designed for pressurized
venting.
4. An induced draft fan for the chimney may be neces-
sary if:
• Excessive resistance to flow of combustion gases can
be expected.
• Cross-sectional area of chimney is smaller than mini-
mum recommended.
• Chimney height is less than recommended.
5. When using an induced draft fan:
• Seal all vent joints.
• Interlock burner with fan operation.
Part number 550-142-182/1014
13