Zoning with the EVG Control
(continued)
D. Zoning with ZONE VALVES, multiple boilers, suggested applications
(see EVG Boiler Manual for single boiler suggested applications)
WMZV zone valve zone controller plus DHW controlled by boiler, Optional DHW
This suggested application only applies to systems with DHW piped directly to individual boilers. For systems
with DHW connected to the system, other control arrangements may be required.
The wiring shown here will also work for a system as in Typical Application B on page 18. This uses two systems
piped in parallel. If the space heating system pump is turned off, no heat is delivered to the space heating loop.
1. Review wiring information on page 27 (120 VAC
outputs) and page 28 (24 VAC inputs).
2. This application example provides domestic pri-
ority by using the EVG control(s). Space heating
pumps will operate when called on by the zone
controller, but no heat will be delivered to the
system — the boiler circulator will not run during
DHW heating.
3. The configuration at right uses INPUT 2 on any
boiler for space heating with the call for heat com-
ing from the zone controller (X-X).
4. INPUT 1 is connected to a DHW aquastat.
5. This configuration applies to either a local demand
(direct-piped to a single boiler) or a network de-
mand (piped to the main system).
6. Suggested for space heating: Assign INPUT 2 to
either LOCAL PRIORITY 2 (direct) or NETWORK
PRIORITY 2 (system). To set up the priority,
choose the space heating system type that matches
the heating system during the WIZARD setup or
manually in the priority menu.
7. Suggested for DHW: Assign INPUT 1 to LOCAL
PRIORITY 1. Wire the DHW circulator to OUT-
PUT 1. Set the control for boiler pump OFF during
DHW calls.
8. Use the factory default settings for DHW and
for the heating system type chosen, or change if
needed. Factory defaults should work for other
settings not listed above.
P15, P11, and P2 are terminal strips on the EVG control.
Part number 550-100-193/0817
– 39 –
®
CONDENSING GAS BOILER70/110/155 Advanced Manual