User Guide
®
CONDENSING GAS BOILER — 70/110/155 Advanced Manual
Part number 550-100-193/0817
– 16 –
Fast-Track Setup — Typical Application A (cont.)
Boiler Model, Altitude and Fuel Type are critical settings. Failure to set correctly could result in severe personal
injury, death or substantial property damage.
SETUP FOR Figure 8, page 14 AS SHOWN (DHW directly connected)
Boiler Wiring and Control Settings
(See Figure 8, page 14 for items referenced)
Boiler
ID
TT
input
Wired
from:
Input
Assignment
Aux
Option
Output
Wired to:
***
1
Master
1 Zone 1 Tstat Priority 2 - Network 1 N/A 1 Zone 1 Circ/Valve
2 Zone 2 Tstat Priority 2 - Network 1 N/A 2 Zone 2 Circ/Valve
3 No Wire Aux Pump/Output * Any TT Input By It's Priority Settings 3 System Circ Relay *
2
Shadow
1 DHW Aquastat Priority 1 - Local 1 N/A 1 DHW Circ.
2 Zone 3 Tstat Priority 2 - Network 1 N/A 2 Zone 3 Circ/Valve
3 Zone 4 Tstat Priority 2 - Network 1 N/A 3 Zone 4 Circ/Valve
* System circulator will not be used if system is circulator zoned. Aux Pump/Output would not be required.
An additional Zone Circ. could be used here, instead.
Priority Settings
Priority # Setting Value Priority # Setting Value
Priority 1 – Local 1
(Boiler 2 only)
System Type DHW
Priority 2 – Network 1
(Boiler 1 only)
System Type
Select heating
system type
Run Blr Pump NO Run Blr Pump YES
Run Aux Output NO Run Aux Output YES
SETUP IF DHW IS LOCATED IN SYSTEM AS A ZONE
Boiler Wiring and Control Settings
(See Figure 8, page 14 for items referenced)
Boiler
ID
TT
input
Wired
from:
Input
Assignment
Aux
Option
Output
Wired to:
***
1
Master
1 Zone 1 Tstat Priority 3 - Network 2 N/A 1 Zone 1 Circ/Valve
2 Zone 2 Tstat Priority 3 - Network 2 N/A 2 Zone 2 Circ/Valve
3 No Wire Aux Pump/Output * Any TT Input By It's Priority Settings 3 System Circ *
2
Shadow
1 DHW Aquastat Priority 2 - Network 1 N/A 1 DHW Circ/Valve
2 Zone 3 Tstat Priority 3 - Network 2 N/A 2 Zone 3 Circ/Valve
3 Zone 4 Tstat Priority 3 - Network 2 N/A 3 Zone 4 Circ/Valve
* System circulator will not be used if system is circulator zoned. Aux Pump/Output would not be required.
An additional Zone Circ. could be used here, instead.
Priority Settings
Priority # Setting Value Priority # Setting Value
Priority 2 – Network 1
System Type DHW
Priority 3 – Network 2
System Type
Select heating
system type
Run Blr Pump YES Run Blr Pump YES
Run Aux Output YES Run Aux Output YES
*** Outputs are 120 VAC maximum 2.0 amps. Use relay for other voltages or higher amperages.
Figure 9 Typical Application A — multiple boiler system — setup requirements (parameters not listed below can be
left at factory default settings unless special needs indicate different settings)