Brochure

In the interest of continual improvements in product and performance,
Weil-McLain reserves the right to change specifications without notice.
*Evergreen 399 ratings are gross output and combustion eciency
MODEL EVG 70 EVG 110 EVG 155 EVG 220 EVG 299 EVG 399
CSA INPUT (MBH) 70 110 155 220 299 399
DOE HEATING CAPACITY (MBH) 65 101 143 206 280 383*
NET AHRI (MBH) 57 88 124 179 243 333
DOE AFUE 95.2% 95.0% 95.1% 95.0% 95.0% 96.5%*
VENT MATERIAL
PVC, CPVC,
PP, SS
(AL29-4C)
PVC, CPVC,
PP, SS
(AL29-4C)
PVC, CPVC,
PP, SS
(AL29-4C)
PVC, CPVC,
PP, SS
(AL29-4C)
PVC, CPVC,
PP, SS
(AL29-4C)
PVC, CPVC,
PP, SS
(AL29-4C)
VENT/COMBUSTION AIR
CONNECTION DIAMETER
3" 3" 3" 4" 4" 4"
VENT/COMBUSTION AIR PIPE SIZE 2" or 3" 3" 3" 3" or 4" 4" 4"
VENTING LENGTH 100' 100' 100' 100' 100' 100'
MIN. RECOMMENDED PIPE SIZE 1" 1" 1¼" 1¼" 1½" 1½"
SUPPLY/RETURN TAPPING 1" 1" 1¼" 1½" 1½" 1½"
GAS CONNECTION SIZE
½" ½" ½" ¾" ¾" ¾"
APPROX. SHIPPING WEIGHT (Lbs.) 125 125 145 215 260 260
WATER VOLUME (Gal.) 2.5 2.5 3.2 4.6 7.0 6.7
FEATURES:
BOILER
CONTROL FEATURES
VENTING*
JACKET ASSEMBLY
Stainless steel fire-tube heat
exchanger
Non-metallic heat exchanger
base
Floor standing or wall-mount
Natural or LP gas
Negative regulated combustion
5 to 1 turndown ratio (70-155)
10 to 1 turndown ratio (220-399)
Boiler circulator
- Taco ECM 007e (70/110)
- Taco ECM 0015e (155)
- Taco 0014 (220/299)
- Taco 0013 (399)
Propane conversion kit
Low water cut-o
Water treatment – inhibitor &
test kit
Easy installation with Setup
Wizard
Zone and/or priority based
control
Three thermostat inputs
Outdoor reset for each priority
Rate adjustable per priority
0-10V input (modulation or
setpoint)
Four total outputs
- 1 dedicated boiler circulator
output
- 3 additional outputs can
be used with circulators,
dampers, or system aux
Aux inputs – flow switch or end
switch
Aux outputs – system pump or
damper
Modbus® connectivity
Additional heat demand contact
Direct vent 100 ft. for intake and
100 ft. for vent
Dual pressure zones (220-399)
Common combustion air
Fully removable jacket front
door
Adjustable boiler legs
On/o power switch (220-399)
Line voltage service receptacle
(220-399)
Mounting bracket ready for
wall-mount kit
- Shipped standard with 70-155
- Optional kit for 220-399
Condensate trap
OPTIONAL EQUIPMENT:
Wall-mount kit (220-399)
Concentric vent kit
Condensate neutralizer kit
Sidewall vent/air termination kit
Maintenance kits
*Please call your local Weil-McLain sales oce for additional venting options
SPECIFICATIONS