Install Instructions

&IGURE $)!'./34)#3 menu details (continued) (see Figure 68, page 65 for access information)
Part number 550-100-131/0715
– 81 –
GAS-FIRED WATER BOILERBoiler Manual
DIAGNOSTICS menu (continued)
-ENU)TEM #OMMENT
2UN4IMES
"URNER4IME
Displays cumulative time the burner has been active (can be increased by user)
2OTATE4IME
Records the days of operation passed from the last time the Master boiler rotated the firing sequence.
)NPUT4IME
Displays cumulative time that Input 1 has been closed (Or 0-10V t 1 volt)
)NPUT4IME
Displays cumulative time that Input 2 has been closed
)NPUT4IME
Displays cumulative time that Input 3 has been closed
.ETWORK4IME
Records time this boiler was running on a network call for heat generated by the Master boiler
)GNITION#OUNT
Displays total number of successful ignitions
-ASTER3HADOW
#OMM
"OILER)$
Displays boiler control type and ID number
,INKEDTO-ASTER
Shows if control is currently linked to a Master control
"OILERSON.ETWORK
Shows number of boilers currently on network
2EQUESTEDTO2UN
Shows if this control is being requested to satisfy a network call
4YPE
Shows whether the control is Network-P1, Network-P2, or NONE
2EQUESTED-OD2ATE
Rate coming from the Master
-AX"OILER4EMP
Displays maximum allowable boiler temperature
"OILER/N$IFF
Temperature differential from master boiler for network priorities
"OILER/FF$IFF
Temperature differential from master boiler for network priorities
.ETWORK"OILERS &ORMULTIPLEBOILERSONLYn3EE%6'!DVANCEDMANUAL

Shows current rate of boiler
&
Shows Boiler Out temperature of boiler

Shows priority being satisfied, updated based on active demand

Shows system type of call for heat, updated based on active demand
/&
Shows the sequence position of that boiler in all the boilers available
",2
Shows boiler number this data belongs to
.ETWORK)NPUTS
"OILERNUMBER
Displays boiler number
)NPUTS
Displays inputs configuration and whether it is active. If input is active, it will be displayed in BOLD print
3OFTWARE6ERSIONS
Display Software version of the microprocessor on the display circuit board
Main Micro Software version of the main microprocessor on the control circuit board
Second Micro Software version of the second microprocessor on the control circuit board
4/2%3%4!,,
()34/29#/5.4%23
4/:%2/
To reset all history counters to zero: Enter the DIAGNOSTICS menu. Then press and hold the left and right arrows
located below the control display. Hold for 5 seconds. This will cause ALL history to be deleted. To maintain
history, reset counters individually.
#ONTROL&AULT
Displays number of control faults
)GNITION2ETRIES
Displays cumulative ignition attempts. It is recommended that his be reset during yearly maintenance by holding down the Left and
Right arrows or by selecting this line and pressing the Enter button
-ANUAL2ESET#NT
Displays number of manual reset lockouts since last cleared
!UTO2ESET#NT
Displays number of auto reset lockouts since last cleared
,OCKOUT(ISTORY
Choose this to view the most recent error recorded
&AULT.AME
Displays the name of the fault that occurred
&AULT4YPE
Displays the type of fault that occurred