Install Instructions
&IGURE
Air silencer removal
&IGURE Removal of Natural gas venturi
&IGURE Installing the new propane gas venturi
Part number 550-100-131/0715
– 14 –
™
GAS-FIRED WATER BOILER — Boiler Manual
&IGURE
Gas pipe loosened for propane conversion
3. If the jacket front door was not already removed, remove it.
4. Locate the blower and venturi (see Figure 11).
5. Gently pull on both silencer retaining clips (Figure 11, item
2) and remove air silencer from front of venturi (item 3).
6. Disconnect wire harness from gas valve.
,%'%.$for Figures 11, 12, 13 and 14
Air Silencer
Air silencer clips (2)
Venturi
Blower
Gas valve
Gas pipe
Swivel nut
Garlock Washer
7. Loosen swivel nut (Figure 11, item 7) on venturi-gas valve
connection (item 6). See Figure 12. Gently set gas valve a side.
8. Remove three (3) slotted T20 Torx screws holding the
venturi, (3, Item 3) in place. Remove venturi, o-ring, and
inspect blower surface. Discard old o-ring and washer
gasket. See Figure 13.
9. Install new propane venturi and o-ring from conversion kit.
10. Make sure o-ring is seated properly in groove on blower.
11. Insert three (3) new slotted Torx screws from conversion
kit to hold venturi in place. Torque screws to no more than
23 inch-pounds.
12. Reassemble gas pipe with new fiber washer from conversion
kit to the venturi connection, using two wrenches to tighten
Gas conversions (continued)
5SETWOWRENCHES when tightening gas piping at
boiler, using one wrench to prevent the boiler gas
line connection from turning. Failure to support
the boiler gas connection pipe to prevent it from
turning could damage gas line components.
4
8
3
7
5
5
3
1
7
2
6
3
4
3